background image

September 2002

83-KRS100-001

4

KRS-100 Nitrogen Releasing System

but bends must be made so that the tubing will not flatten

or kink. A single coil of tubing approximately 2-1/2 inches in

diameter is desirable at each flare or compression fitting.

The coil may be neatly made by wrapping the tubing around

any convenient cylindrical object of that diameter.
When sliding the tubing through conduit the leading end of

the tube should first be crimped and bent double so as to

provide a smooth sliding surface and to prevent possible

foreign matter in the conduit from entering the tubing. All

tubing fittings with pipe threads, as at the KRS-100 actua-

tor valve body, the pressure-operated actuator and other

accessory devices, shall be assembled with Teflon tape

wrapped around the male pipe threads.
All tubing should be blown out with air or nitrogen prior to

making final connections. Table 1 summarizes the length

of tubing allowed per each KRS-100 cylinder.

3-1.4

Control Head Mounting

(To Actuator Valve Assembly)

Note:

The system control head must be mounted to the

KRS-100 actuator valve body using the mounting kit

(P/N 06-129706-001) supplied with the Actuator Valve

Assembly (P/N 83-100010-001).

This kit contains a rubber gasket that must be placed be-

tween the mating surfaces of the actuator body and the

control head housing. This kit also contains Teflon coated

bolts and nylon washers for fastening the actuator valve

assembly to the control head housing.
Prior to mounting a control head on the KRS-100 actuator

valve assembly make certain of the following:
1. The control head is in the 

SET 

position. On mechani-

cal  installations  the  manual  release  lever  should  be

pushed up and the tensioning tool inserted in safety

hole in the housing. On electrical installations make

certain the solenoid trigger holds the actuating lever.

The actuating cam arrow should be pointed away from

the ratchet spool, (toward the 

SET 

position on face-

plate), and the release plunger should be flush or slightly

retracted within the control head body.

2. Ensure the safety pin is in place on the actuator valve

assembly. See Figure 2.

3. Do not install the nitrogen cartridge at this time.

Note:

Control Heads are shipped in the 

SET 

position with

cover  off  for  ease  of  installation.  There  are

tensioning tools shipped with the mechanical and

tandem  control  heads  to  enable  proper  tension

setting on the cable. A tensioning tool may be used

with  the  pneumatic  control  heads.  There  is  no

tensioning tool permitted with the electrical control

heads. The plunger of the electric solenoid holds

the control head mechanism in proper position for

the 

SET

 position.

4-1

SYSTEM CHECK-OUT

To demonstrate proper operation of the actuating system

the following check-out is to be accomplished 

prior to in-

stalling the nitrogen cylinder (P/N 83-100004-001)

.

4-1.1

For Control Head Operation

1. Remove the tensioning tool (when used) from the safety

hole in the control head. If the system is properly in-

stalled, the head should remain in the 

SET 

position,

fully prepared for either automatic or manual opera-

tion.

2. Remove safety pin from actuator valve assembly.
3. All cables, with the exception of remote pull cables,

should be in a taut condition if properly installed.

4. For fusible link check-out, cut the “S” hook farthest from

the control head (terminal link). The released tension

should permit the control head to operate, triggering

the releasing mechanism.

5. Check to see that the actuating cam is in the operated

position and that the actuating cam (shaft arrow) has

rotated to the released position. All cables should be

slack, including remote cable.

6. To check out electrical control heads, do the following:

Ensure that the actuating cam (shaft arrow) is turned

to the 

SET 

position. Energize the control head by ap-

plying heat directly to the thermostats or operating the

panel.

7. Check that the control head triggering mechanism has

released. Check that the actuating cam arrow has ro-

tated to the release position.

8. Check to see that the gas valve and/or electric shut-off

have operated. Slack in the cable is an indication, but

only the shut-off of gas and/or shut-off of electric cur-

rent to the hazard demonstrates that these units have

properly functioned.

9. Inspect all other aspects of system operation, such as

dampers and door holders to see that the system has

been installed properly.

10. After resetting the system as outlined below, repeat

check-out by operating local and remote manual con-

trols to assure their operation.

5-1

READYING THE SYSTEM

If all conditions have proven to be operational, place sys-

tem in operation as follows:
1. If the fusible link system is used, install a new “S” hook

in the detection line. If the electric system is used, re-

placements should not be required.

2. Reset the control head.
3. Remove the control head tensioning tool when done,

and  discard.  Electric  control  heads  do 

not

  use

tensioning tools.

Summary of Contents for KRS-100

Page 1: ...KRS 100 Nitrogen Releasing System Application Operation and Maintenance Manual P N 83 KRS100 001 September 2002 FM APPROVED UL Listing File No EX 3559 EX 2153 ...

Page 2: ......

Page 3: ...g 3 3 1 3 1 Tubing and Fittings 3 3 1 4 Control Head Mounting To Actuator Valve Assembly 4 4 1 System Check Out 4 4 1 1 For Control Head Operation 4 5 1 Readying the System 4 6 1 Inspection And Maintenance 5 6 1 1 KRS 100 Assembly Condition 5 6 1 2 Nitrogen Cylinder Pressurization 5 6 1 3 Detection and Actuation 5 List of Figures 1 KRS 100 System Detail w POA 87 100012 001 2 2 KRS 100 System Detai...

Page 4: ...September 2002 83 KRS100 001 KRS 100 Nitrogen Releasing System THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 5: ...tches can be installed on the KRS 100 actuation line Multiple KRS 100 releasing units may be used when the number of agent storage cylinders exceeds the maximum capacity of one KRS 100 releasing unit The KRS 100 sys tem is fully modular and is expandable to fit any size appli cation Two or more KRS 100 cylinders may be used when utiliz ing two or more different types of detection to cover the same...

Page 6: ...NT CHECK P N WK 877810 000 OPTIONAL P N 06 129706 001 100 FT MAX 1 4 INCH COPPER TUBING 3 THREE PRESSURE SWITCHES AND 10 TEN CYLINDERS 50 FT MAX 1 4 INCH COPPER TUBING OUTLET CYLINDER Figure 1 KRS 100 System Detail w POA 87 100012 001 WET OR DRY CHEMICAL SYSTEM CYLINDER SYSTEM VALVE ACTUATOR P N 87 120042 001 APPROX 2 1 2 INCHES IN DIA VENT CHECK P N WK 877810 000 OPTIONAL OR ADDITIONAL CYLS MOUNT...

Page 7: ... clearance See Figure 3 3 1 3 Tubing Connect actuation tubing to the outlet on the KRS 100 ac tuator valve body Ream and thoroughly clean all chips and cutting oil from the inside of tubing prior to connection All tubing is to be securely supported no more than ten feet on centers See Table 1 for tubing limitations Table 1 Tubing Limitations x a M n i M m e t s y S l a t o T t f 0 5 1 t f 5 l o r ...

Page 8: ...enable proper tension setting on the cable A tensioning tool may be used with the pneumatic control heads There is no tensioning tool permitted with the electrical control heads The plunger of the electric solenoid holds the control head mechanism in proper position for the SET position 4 1 SYSTEM CHECK OUT To demonstrate proper operation of the actuating system the following check out is to be ac...

Page 9: ... given to KRS 100 Assembly Condition Nitrogen Cylinder Pressurization Ensure that it is at proper weight Note Nitrogen cylinder full weight includes the shipping cap ensure that it is installed prior to weighing Detection and Actuation System Actuation Tubing Auxiliary Equipment 6 1 1 KRS 100 Assembly Condition The actuator valve assembly must be inspected internally for nicks dents and scratches ...

Page 10: ...September 2002 83 KRS100 001 6 KRS 100 Nitrogen Releasing System THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 11: ......

Page 12: ...he Kidde Fenwal Quotation Acceptance of Order and or Original Invoice which will become part of your sales agreement Please contact Kidde Fenwal directly for a return material authorization RMA number before returning material to the factory at Ashland Massachusetts shipment prepaid Kidde Fenwal will repair or replace and ship prepaid These instructions do not purport to cover all the details or v...

Reviews:

Related manuals for KRS-100