17
10
T
ECHNICAL SPECIFICATION
Environment
Ambient Temperature Range
-10 to 50 degrees Celsius
Dust and water rating
IP66
Power related specification
Input voltage
6 to 28 VDC
Maximum power usage
5 Watt
Maximum voltage VFC
30 VDC
Maximum current VFC
1 A
Backup power duration
Typically, 4 hours in idle state
Sounder / beacon voltage main powered mode
20
–
22 VDC
Sounder / beacon alarm maximum current
50 mA / 100 mw
Sounder / beacon voltage battery powered mode
9
–
11 VDC
Sounder / beacon alarm maximum current
50 mA / 50 mw
Voltage in battery powered mode or when sounder / beacon is off 9
–
11 VDC
Voltage in main powered mode and when sounder / beacon is on 20
–
22 VDC
Connector and cable specification
Conductor cross section solid (Cross Sectional Area mm²)
0.5 mm² ... 1.5 mm²
Conductor cross section flexible (Cross Sectional Area mm²)
0.5 mm² ... 1.5 mm²
Conductor cross section AWG
20 ... 16
Stripping length
8 mm
Maximum cable length of extinguish and fire zone connections 100 m
Maximum cable length of all other connections
30 m
Extinguisher output specification
End of line component
Diode with anode connected to + connection
Advised diode
1N5400, RL201, SF21
Maximum extinguisher count
5 connected in series
Extinguisher release current
Between 1,3 and 1,6 A
Extinguisher release pulse length
Between 50 and 55 ms
Detection zone, hold and extinguishing release inputs
Normal state
> 8
kΩ <
12
kΩ
Alarm load
< 100
Ω >1.2
kΩ
Zone fault threshold 1
< 100
Ω
Zone fault threshold 2
> 1.2 k
Ω < 8
kΩ
Zone fault threshold 3
> 12
kΩ
Alarm resistant
470
Ω
End of line resistant
10 k
Ω