10
5.8. Factory defaults.
Return to standard settings set by the producer by choosing
[Prod]
and pressing
OK button. After activating this function, the controller sets each parameter showed in
the table 2.
5.9. Testing outputs.
To make checking the controller work easier, it is possible to test output circuits
which control the fan and the pump, and the circuit which controls additional
equipment. This function is available in service mode, only if the control process is off,
i.e. the controller was in STOP mode before switching to service mode. By choosing
[outP]
on the display and pressing OK button you can turn on the central heating
pump for a while, by choosing
[outΠ]
and pressing OK you can turn on the pressure
fan and by choosing
[outr]
and pressing OK you can turn the additional equipment on
(if the additional module is connected). Choosing
[outu]
allows testing the hot water
pump output.
5.10. Exiting service mode.
By choosing
[End ]
option on the display and pressing OK button you can quit
parameter setting mode. The controller also quits service mode, when no buttons are
pressed for 1 minute.
6. Additional functions.
To improve comfort in heated rooms, the controller has been equipped with an input
allowing to connect any kind of room thermostat with contact output. When
temperature in the room is below desired temperature, the central heating pump is
turned on and the room thermostat indicator is lit. It means that the boiler should keep
temperature set by the room thermostat knob. After reaching desired temperature in
the room, the room thermostat indicator turns off, the central heating pump is turned
off and the boiler switches to mode in which it keeps burning at minimum temperature.
CAUTION
. In case of not having room thermostat in the system, the room thermostat
input contacts must be short-circuited.