KEY RK-2001E2 Operation Manual Download Page 9

9

Warning!

If neither contact thermostat nor indoor temperature sensor is used, the

connection should be short-circuited.

6. Device failures.

The controller is constantly testing if its internal circuits and temperature sensor are

working correctly. After detection of fault, it stops the pressure fan, turns on the

circulating pump and shows proper error message on the display. In case of failure

please turn off the controller, plug the circulating pump to the power source, bypassing

the controller, ensure appropriate fuel firing in the boiler and contact the service. When

[E 1]

error appears on the display, it means fault (short-circuit) in the boiler sensor

circuit or temperature below -9°C.

[E 2]

is displayed if boiler overheats.

[E 3]

error

means fault and overheating at the same time. Appearing of

[E 1]

error on the display

without ability to cancel it by pressing STOP button, in spite of temperature below

90°C, may mean permanent damage of boiler temperature sensor (e.g. if the boiler

overheated above 150°C).

7. Device removal.

In case of need to remove the controller from the system:

– turn the master switch off,

– disconnect the power of the boiler,

– remove the controller from the slot in the boiler,

– disconnect all connectors with cords from the controller.

8. Specifications.

Voltage:

230V ± 10%, 50Hz

Power consumption:

<4VA

Temperature measurement range:

-9–109°C ± 1°C

Boiler temperature adjustment range:

30–90°C ± 1°C

Programmable boiler overheating protection:

90 –99°C ± 1°C

Hardware boiler overheating protection:

>95°C ± 1°C

Circulating pump launch temperature:

30–70°C ± 1°C

Fan out:

total max 2A/230V

Dimensions:

80 x 170 x 100 mm

Summary of Contents for RK-2001E2

Page 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001E2 Version 9A15 ...

Page 2: ......

Page 3: ...placed in measurement hole in the boiler Picture 2 shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CAUTION The maximum total power of devices connected to the controller mustn t exceed 450W CAUTION As additional option you can connect the UM 1 module...

Page 4: ...iler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode which controller currently is in for example 50º STOP mode 50ºC WORK mode 50ºc keeping fire in WORK mode 4 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change programmed ...

Page 5: ...trolling emergency cooling system 4 output controlling extra devices turning on during work of blow in fan 0 4 1 0 Prod Return to factory defaults outP Central heating pump testing outP out1 outΠ Fan output testing outΠ out2 outr Additional output testing outr out3 End Exit the service mode In the table above the first column represents example display indications in the next columns there are par...

Page 6: ...water in the boiler which causes start of the circulating pump Circulating pump works independently from the control process and is launched additionally in case of boiler overheat Circulating pump launch hysteresis Ph 2 this parameter defines what value should temperature decrease by below circulating pump launch temperature to turn the pump off The work mode and pause time of CH pump Pc 2 in STO...

Page 7: ...to previous mode by pressing STOP button No fuel testing time during fuel firing is finished after the set temperature is achieved No fuel testing time during work mode Fb30 in WORK mode if temperature of water in the boiler decreases below temperature set with the thermostat by hysteresis value and does not increase by 2 C in the programmed time the control process will be turned off and the disp...

Page 8: ...s set by the producer by choosing Prod option in service mode and pressing OK button After activating this function the device sets each parameter showed in the table to default 4 9 Exiting service mode By choosing End option on the display and pressing OK button you can quit service mode The device also quits service mode when no buttons are pressed for 1 minute 5 Additional functions In order to...

Page 9: ...ed if boiler overheats E 3 error means fault and overheating at the same time Appearing of E 1 error on the display without ability to cancel it by pressing STOP button in spite of temperature below 90 C may mean permanent damage of boiler temperature sensor e g if the boiler overheated above 150 C 7 Device removal In case of need to remove the controller from the system turn the master switch off...

Page 10: ...10 Picture 2 RK 2001E2 connection scheme Picture 3 UM 1 module connection scheme ...

Page 11: ... Pc 2 The work mode and pause time of CH pump L 40 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd60 Fuel shortage testing time with burning Fb30 Fuel shortage testing time in WORK mode and burning out Ar 0 Work mode of extra output 0 output turning on extra boiler 1 alarm output 2 output controlling mixing valve 3...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohaterów Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl ...

Reviews: