KEY RK-2001E2 Operation Manual Download Page 8

8

being opened and closed depending on the room thermostat input. Additionally, mixing

valve is opened in case of overheating or boiler temperature sensor malfunction.

[Ar 3] mode

– output may control boiler emergency cooling system (e.g. pump). In this

mode the additional output is turned on in case of boiler overheating or boiler

temperature sensor error alarm.

[Ar 4] mode

– output may control devices working together with blow-in fan.

CAUTION.

Equipment should be connected to additional output using UM-1module.

Connection schemes are shown on picture 3.

4.7. Testing of device's outputs.

To make checking the controller work easier, it is possible to test output circuits which

control the fan and the pump, and the circuit which controls additional boiler. This

function is available in service mode, only if the control process is off, i.e. the controller

was in STOP mode before switching to service mode. By choosing

[outP]

on the

display and pressing OK button you can turn on the circulating pump for a while, by

choosing

[outΠ]

and pressing OK you can turn on the pressure fan and by choosing

[outr]

and pressing OK you can turn the additional boiler, the alarm signaling system

or the mixing valve servo-motor on (if the additional module is connected).

4.8. Factory defaults.

You can return to standard settings, set by the producer, by choosing

[Prod]

option in

service mode and pressing OK button. After activating this function, the device sets

each parameter showed in the table to default.

4.9. Exiting service mode.

By choosing

[End ]

option on the display and pressing OK button you can quit service

mode. The device also quits service mode, when no buttons are pressed for 1 minute.

5. Additional functions.

In order to improve comfort in heated rooms the controller is equipped with indoor

temperature sensor connection. RK-2001E2 compares measured room temperature

with value set with room thermostat knob. When the temperature is lower than desired

temperature circulation pump is turned on and room thermostat indicator is lit, which

means that boiler should keep temperature set with boiler thermostat knob. When

desired room temperature is reached circulation pump and indicator are turned off and

the boiler enters fire keeping mode and works at minimal temperature.

Design of the controller allows connecting any contact thermostat in place of indoor

temperature sensor. Shorting of this thermostat contacts when room temperature is

low will start heating procedure described earlier. When contacts aren't shorted the

controller keeps minimal boiler temperature.

Warning!

When contact thermostat is connected in place of indoor temperature

sensor, the value set with controller room thermostat knob won't affect the controller

operation, and room temperature will depend only on value set on contact thermostat.

Summary of Contents for RK-2001E2

Page 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001E2 Version 9A15 ...

Page 2: ......

Page 3: ...placed in measurement hole in the boiler Picture 2 shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CAUTION The maximum total power of devices connected to the controller mustn t exceed 450W CAUTION As additional option you can connect the UM 1 module...

Page 4: ...iler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode which controller currently is in for example 50º STOP mode 50ºC WORK mode 50ºc keeping fire in WORK mode 4 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change programmed ...

Page 5: ...trolling emergency cooling system 4 output controlling extra devices turning on during work of blow in fan 0 4 1 0 Prod Return to factory defaults outP Central heating pump testing outP out1 outΠ Fan output testing outΠ out2 outr Additional output testing outr out3 End Exit the service mode In the table above the first column represents example display indications in the next columns there are par...

Page 6: ...water in the boiler which causes start of the circulating pump Circulating pump works independently from the control process and is launched additionally in case of boiler overheat Circulating pump launch hysteresis Ph 2 this parameter defines what value should temperature decrease by below circulating pump launch temperature to turn the pump off The work mode and pause time of CH pump Pc 2 in STO...

Page 7: ...to previous mode by pressing STOP button No fuel testing time during fuel firing is finished after the set temperature is achieved No fuel testing time during work mode Fb30 in WORK mode if temperature of water in the boiler decreases below temperature set with the thermostat by hysteresis value and does not increase by 2 C in the programmed time the control process will be turned off and the disp...

Page 8: ...s set by the producer by choosing Prod option in service mode and pressing OK button After activating this function the device sets each parameter showed in the table to default 4 9 Exiting service mode By choosing End option on the display and pressing OK button you can quit service mode The device also quits service mode when no buttons are pressed for 1 minute 5 Additional functions In order to...

Page 9: ...ed if boiler overheats E 3 error means fault and overheating at the same time Appearing of E 1 error on the display without ability to cancel it by pressing STOP button in spite of temperature below 90 C may mean permanent damage of boiler temperature sensor e g if the boiler overheated above 150 C 7 Device removal In case of need to remove the controller from the system turn the master switch off...

Page 10: ...10 Picture 2 RK 2001E2 connection scheme Picture 3 UM 1 module connection scheme ...

Page 11: ... Pc 2 The work mode and pause time of CH pump L 40 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd60 Fuel shortage testing time with burning Fb30 Fuel shortage testing time in WORK mode and burning out Ar 0 Work mode of extra output 0 output turning on extra boiler 1 alarm output 2 output controlling mixing valve 3...