5.2 - Commissioning

Once all (and not just some) of the system devices have passed the 

testing procedure, the system can be commissioned;

the system’s technical dossier must be produced and kept for 10 

years.  It must contain the electrical wiring diagram, a drawing or 

photograph of the system, the analysis of the risks and the solutions 

adopted to deal with them, the manufacturer’s declaration of con-

formity for all connected devices, the operator’s manual for every 

device and the system maintenance plan;

fix a dataplate with the details of the automation, the name of the 

person who commissioned it, the serial number and year of con-

struction and the CE marking on the gate or door;

also fit a sign specifying the procedure for releasing the system by 

hand;

draw up the declaration of conformity, the instructions and precau-

tions for use for the end user and the system maintenance plan and 

consign them to the end user;

ensure that the user has fully understood how to operate the system 

in automatic, manual and emergency modes;

the end user must also be informed in writing about any risks and 

hazards still present;

WARNING  - 

after detecting an obstacle, the gate or door stops 

during its opening travel and automatic closure is disabled; to re-

start operation, the user must press the control button or use the 

transmitter.

5 - TESTING AND COMMISSIONING THE AUTOMATION SYSTEM

5.1 - Testing

All system components must be tested following the procedures de-

scribed in their respective operator’s manuals;

ensure that the recommendations in Chapter 1 - Safety Warnings - 

have been complied with;

check that the gate or door is able to move freely once the automa-

tion system has been released and is well balanced, meaning that it 

will remain stationery when released in any position;

check that all connected devices (photocells, sensitive edges, 

emergency buttons, etc.) are operating correctly by performing gate 

or door opening, closing and stop tests using the connected control 

devices (transmitters, buttons or switches);

perform the impact measurements as required by the EN12445 

standard,  adjusting  the  control  unit’s  speed,  motor  force  and  de

-

celeration functions if the measurements do not give the required 

results, until the correct setting is obtained.

The  system  must  be  tested  by  a  qualified  technician,  who  must 

perform the tests required by the relevant standards in relation to 

the risks present, to check that the installation complies with the

relevant regulatory requirements, especially the EN12445 standard 

which specifies the test methods for gate and door automation sy

-

stems.

Summary of Contents for CT202

Page 1: ...para dois motores 230 Vac 120 Vac para portões de batente Centrala dla dwóch silników 230 Vac 120 Vac do bram skrzydłowych CT202 Istruzioni ed avvertenze per l installazione e l uso Instructions and warnings for installation and use Instrucciones y advertencias para su instalación y uso Anleitungen und Hinweise zu Installation und Einsatz Instruções e advertências para a instalação e utilização In...

Page 2: ... Product Electric connections Display during normal operation Autolearning of the travel stroke Customising the system BASIC MENU Connecting the radio receiver Testing and commissioning Testing Commissioning Further details ADVANCED MENU Instructions and warnings for the final user EC declaration of conformity pag 15 pag 16 pag 16 pag 16 pag 16 pag 17 pag 17 pag 18 pag 18 pag 19 pag 20 pag 22 pag ...

Page 3: ...e with the following safety precautions never make any modifications to part of the automation system other than those specified in this manual Operations of this type can only lead to malfunctions The manufacturer declines all liability for damage caused by unauthorised modifications to products do not allow parts of the automation system to be immersed in water or other liquids During installati...

Page 4: ... DOWN pushbutton 12 SS STEP STEP pushbutton 13 Safety device dip switch 14 F3 Safety fuse for AC accessories electric lock 2 A quick acting 15 F2 Safety fuse for DC accessories 500 mA quick acting 16 F1 Safety fuse for power line 6 3 A quick acting 2 3 Models and technical characteristics CT202 control unit is equipped with a display to enable simple pro gramming and constant monitoring of input s...

Page 5: ...s III overvoltage ensure that all the material used for installation complies with the relevant regulatory standards The cables used must be suitable for the type of installation for example an H03VV F type cable is recommended for indoor appli cations while H07RN F is suitable for outdoor applications TECHNICAL SPECIFICATIONS Power supply L N 230 Vac 10 15 50 60 Hz 120 Vac 10 15 50 60 Hz Max moto...

Page 6: ...OP Eliminates the need to bridge the terminal board inputs WARNING with the dip switch ON the safety devi ces are disabled 4 1 Electrical connections WARNING Before making the connections ensure that the control unit is not powered up 2 3 4 1 1 2 TX RX NC PH2 2 3 4 1 1 2 TX RX PH1 N L 24 Vdc 24 Vac 24 Vac EL EL GND 24 TX PH EDGE EDGE PH2 PH1 STOP OPEN CLOSE PED SS COM L N UP DOWN MENU SS COURTESY ...

Page 7: ... device the contact can be deactivated at any time cutting out the automation system and disabling all functions including Automatic Closure OPEN OPEN command NO contact between OPEN and COM Contact for the HOLD TO RUN function The gate OPENS as long as the contact is held down CLOSE CLOSE command NO contact between CLOSE and COM Contact for the HOLD TO RUN function The gate CLOSES as long as the ...

Page 8: ...UTION if manual programming of deceleration intervals is required go to the next table 1 CAUTION check that mechanical end stops compulsory are present and secure The motors must always reach the mechanical end stop 2 Move the gate manually to mid travel 3 Press the pushbuttons UP and MENU at the same time for at least 5 seconds until LOP is displayed then if necessary press DOWN see figure Ensure...

Page 9: ...n press the SS command Motor M2 stops and motor M1 starts in closing 9 On reaching the point where motor M1 closing deceleration is required press SS M1 motor move ment continues at low speed 10 Precisely when motor M1 reaches the closed position press the SS command Motor M1 stops and restarts in opening 11 On reaching the point where motor M1 opening deceleration is required press SS M1 motor mo...

Page 10: ...MENU If necessary users may select a BASIC MENU which allows modi fication of the control unit s basic parameters To select the BASIC MENU proceed as described below WARNING to be certain of accessing the NORMAL OPERATION display state the starting point for accessing the BASIC MENU press the MENU key twice n PARAMETERS DESCRIPTION DEFAULT CONFIGURATION MIN MAX UNIT 1 TCL Automatic reclosing time ...

Page 11: ...g its opening travel and automatic closure is disabled to re start operation the user must press the control button or use the transmitter 5 TESTING AND COMMISSIONING THE AUTOMATION SYSTEM 5 1 Testing All system components must be tested following the procedures de scribed in their respective operator s manuals ensure that the recommendations in Chapter 1 Safety Warnings have been complied with ch...

Page 12: ...or proportional flashing 0 0 4 13 tC Y Courtesy light duration 0 0 900 s steps of 10s 14 dE A Hold to run 0 disabled 1 enabled 0 0 1 15 se r Cycle threshold for assistance request On reaching the set threshold the subsequent cycles will be performed with quick flashing only if FPr is active 0 disabled 0 0 100 x 1000 cycles 16 se f Enabled in continuous flashing mode for assistance requests functio...

Page 13: ... or power failures while waiting for the engineer to come or for the power to be restored if your system is not equipped with buffer batteries the door or gate can be used just like any non automated installation To do this the manual release procedure must be carried out manual release and operation first bear in mind that the release procedure can only be carried out with the door or gate statio...

Reviews: