![Kewtech KTD40 User Manual Download Page 7](http://html1.mh-extra.com/html/kewtech/ktd40/ktd40_user-manual_1959981007.webp)
12
www.kewtechcorp.com
Kewtech Corporation Limited
Midas House, Unit 2b, Stones Courtyard, High Street, Chesham, Bucks HP5 1DE
T:
01494 792 212
F: 01494 791 826
E: [email protected]
Condition Wiring
Supply
LED
Buzzer
Number
Condition
Terminal
Display
N
E
L
Socket Wiring
1
Correct
N
E
L
Continuous
2
L-E reverse
N
L
E
Warble
3
L-N-E miswire
E
L
N
Warble
4
L-N reverse
L
E
N
Warble
5
L-N-E miswire
L
N
E
Warble
6
Faulty N / L-E miswire
NC
L
N
Warble
7
Faulty N / E miswire
NC
N
L
Warble
8
Faulty N
NC
E
L
Warble
9
Faulty N / L-E reverse
NC
L
E
Warble
10
Faulty E / L-N reverse
L
NC
N
Warble
11
Faulty E
N
NC
L
Warble
12
Faulty E / N miswire
E
NC
L
Warble
13
Faulty E / L-N miswire
L
NC
E
Warble
14
Faulty L / N-E miswire
L
N
NC
Warble
15
Faulty L / E miswire
N
L
NC
Warble
16
Faulty L / N-E miswire
E
L
NC
Warble
17
Faulty L / N miswire
L
E
NC
Warble
18
No Mains
NC NC NC
None
Above is the indication given when touching the touch pad.
LEDs will flash to indicate fault condition NC = No Connection