Kewtech KTD40 User Manual Download Page 4

6

7

 

 

Test lead configuration

Lead configuration for High Current 2-wire testing with TLI feature

The TLI (True Loop Impedence) function is intended for use at distribution boards and 

similar points where you are measuring on the supply side of any Switch/RCD gear.

The TLI measurement function is selected by pressing button 9 labelled ‘Ze/DB’. This 

function uses the maximum high current of the tester and requires the use of the 

distribution board lead set configured in 2-wire mode. Do not use this function with the 

mains lead or the distribution lead set in 3-wire mode.

To arrange the test leads in 2-wire mode pull the blue prod off the blue test lead and 

plug the exposed 4mm connector into the back of the green connector as shown below. 

You will now have the Earth and Neutral leads connected together ready for connection 

to the Earth or Neutral conductor to be tested.

Operation – a Detailed View of the KTD40

 Three LEDs show 

socket wiring 

status

 LCD  - default 

L-N voltage  

measurement

 On/Off button

 No-trip loop select 

(default)

 No-trip PFC 

(prospective fault 

current)

 Push to start test

9  

High current 

loop impedance 

test

 Voltage select 

L-N (default) L-E 

and N-E

 Polarity Test

10  

High current 

PFC test

Reviews: