6
For this example the maximum value is 1667
Ω
, the loop tester
reads 12.74
Ω
and consequently the condition R
A
is
≤
50/Ia is
met. It is also important to test the operation of the RCD using
a dedicated RCD tester in accordance with the international
standard IEC60364 for a TN system. The following condition
shall be fulfiled for each circuit.
Zs
≤
Uo/Ia where Zs is the earth fault loop impedance voltage is
the nominal voltage between phase and earth and Ia is the cur-
rent that causes the automatic disconnection of the protective
device within the time stated in the following table.
Note:
When the protective device is a residual current device
(RCD), Ia is the rated residual operating current 1 n. For
instance ina TN system with a nominal mains voltage of Uo
= 230V protected by type gG fuses the Ia and maximum
Zs values could be:
Uo (Volts
T (seconds)
120
0.8
230
0.4
400
0.2
>400
0.1