Specifications
Measurement specification
Loop impedance
Prospective Short-circuit Current
Voltage
Reference conditions
Ambient temperature:
23±5˚C
Relative humidity:
60±15%
Nominal system voltage
and frequency:
230V, 50Hz
Altitude:
Less than 2000m
Measuring
Nominal test
Intrinsic
Range
range
current at 0
Ω
external
accuracy
loop/Period applied
20
Ω
0.00-19.99
Ω
25A/20ms
200
Ω
0.0-199.9
Ω
2.3/40ms
±(2%rdg+3dgt)
2000
Ω
0-1999
Ω
15mA/280ms
Measuring
Nominal test
Intrinsic
Range
range
current at 0
Ω
external
accuracy
loop/Period applied
200A
0.0-19.99A
2.3A/40ms
2000A
0-1999
25A/20ms
20kA
0.00-4.00kA
25A/20ms
PSC accuracy is
derived from the
loop impedance
accuracy
Measuring range Intrinsic accuracy
180-260V
±(2%rdg+2dgt)