Commissioning
5.1
Carrying out initialisation
Ensure that the separator tank has been topped up to the calm water level with clean water and the distance from the
sensor finger to the water line (calm level) is 50 cm (default configuration).
Plug in the mains plug.
The initialisation of the control unit starts automatically.
During initialisation, the following input is expected:
|Language|
|Date/Time|
|Standard |
|Nominal size |
|Calibration|
For an error-free measurement, the inputs for
|Standard |
,
|Nominal size|
must be entered correctly. The rel-
evant data can be found on the system’s type plate. The
|Calibration|
must be carried out with clean water at the
calm level and correct position of the sensors.
Inputs at the control unit
Selection via the arrow buttons.
Confirm storage in the system memory with
|OK|
.
Initialisation is completed, control unit loads the program memory.
In special installations the control unit may have to be adjusted for the pre-alarm and alarm as described in the enclosed
documentation.
System is ready for operation.
5.2
Make the settings
Set the rest period/measurement interval
Reliable layer thickness measurements are only possible if there is no water inflow to the grease separator at the time of the
measurement, e.g. if the kitchen is currently not in use (at rest). The daily recurring measurement interval must be defined
to take place during this rest period. If the kitchen is in use during the measurement interval, the control unit receives invalid
results. If invalid results are measured over longer periods of the measurement interval, an invalid layer thickness ("--") is
displayed and is entered in the
|1.7 Measured data|
menu.
Determine the daily rest period of the kitchen.
Navigate in the control unit via
|Settings|
and
|Parameters|
to the
|Measuring interval|
menu item
(Password: 1000).
Define the Start and End of the measurement interval and confirm with OK.
Calibrate sensor
Ensure that the separator is topped up with clean water up to the calm (static) level.
Calibrate sensor.
Confirm value with "OK".
The sensor calibration must be repeated after each disposal.