Assembly
45 / 60
V 1.0
Control unit KESSEL Aqualift F Comfort 400V
Custom settings for pumps
S
P
F
1
400
S
P
F
1
500
S
P
F
3
000
S
P
F
4
500
S
P
F
5
500
A
d
ju
s
tme
nt r
ang
e
Co
mm
ent
1
1)
A = Set, check B = Optional C = Changes to be carried out only by trained KESSEL personnel.
Power-up delay [s]
5
5
5
5
5
0…60
B
Sensor height
2
[mm]
2)
Immersion pipe
130
130
130
130
130
0…999
A
Start-up lock [s]
3
3)
Time that elapses before the second pump starts (Duo) as well as the time that elapses before a pump can restart.
6
6
6
6
6
0…30
C
Sensing zone [mm]
1000
1000
1000
1000
1000
0…3000
B
ON1 level [mm]
350
350
350
350
350
0…999
A
ON2 level [mm]
4
4)
Only in Duo version
400
400
400
400
400
0…999
A
OFF1 level [mm]
160
160
160
160
160
0…999
A
Alarm level [mm]
450
450
450
450
450
0…999
A
On delay [s]
1
1
1
1
1
1…10
B
Post run time [sec]
5
5)
Length of delay to switch-off caused by ventilation of the level detector immersion pipe.
- 200l container
3
3
3
2
2
1…10
A
- 300l container
6
6
5
5
3
1…10
A
- 450l container
6
6
6
5
4
1…10
A
Pump mode
6
(Duo only)
6)
Describes the sequence in which the pumps switch on/off. It is possible to switch between alternating and set
sequence.
On
On
On
On
On
Off/On
B
Max. run time
7
[min]
7)
Maximum run time of each pump. Observe pump types S1 and S3.
240
240
240
240
240
40…640
B
Max run occur
8
8)
Maximum number of pump start-ups within 3 minutes. Error message (visual and acoustic) if exceeded.
20
20
20
20
20
5…30
B
Min. current [A]
1
1
1
1
1
0…5
A
Max. current [A]
10
4
6.3
10
14
0…5
A
LEP offset
9
[mm]
9)
Offset required to adjust the pressure created if a compressor is used to create air bubbles.
0
0
0
0
0
0…30
B
Auto SDS [d]
7
7
7
7
7
0…14
B