Compressor set for air bubbling

Art. no. 28048

EN: Installation instructions

NOTE

Note and follow the documentation enclosed with the system

and control unit.
The minimum length of the compressor hose is 1 metre (may

not be shorter).

Prepare the system

Stop wastewater feed to the system.
Pump away residual water manually.
Read off and note the displayed empty level on the display

(mm).

Connect the compressor set

Cut through the compressed air hose as close as possible to

the immersion pipe or submersible pressure switch.
Insert the T-piece into the pressure hose.
Connect the compressed air hose to the small compressor.
Fix the compressor near the control unit.
Plug in the mains plug of the compressor set.

The compressor starts automatically, air bubbling changes

the displayed empty level.

Adjust the configuration of the control unit

Note the changed empty level, determine the difference.

In the menu 

|Settings - Sensor configuration|

Select the setting

 |Pressure Air compres-

sor| 

and confirm. If applicable, take into consideration any

optional alarm float that has been retrofitted.
In the menu 

|Parameter - Air compressor offset

enter the difference amount and confirm (PW: 1000). For

further information, see menu texts in the control unit instruc-

tions.
Immerse in the water vessel to check whether the immersed

depth corresponds to the level displayed on the control unit.

If necessary, further adjust the set air bubbling offset until the

values match.
Restore the wastewater feed.
Perform functional test of the system.

CAUTION

If the offset setting is not adjusted, the pneumatic level

measurement is falsified. The switching points (ON

level) of the system no longer function properly.

Maintenance

Clean the air filter (underside of compressor) as part of the

servicing lifting station maintenance work.