notes:

  Longer chain available on request.
  Opposite hand valves available as cost option (chain on left).
   SCHD2, SECT 7, G16.5 Water Regs. Gaps should be more if water is turbulent – especially if near valve discharge. 40mm 

minimum for valves 1½“ (DN 40mm) or larger – recommended by 

keraFlo

.

   Typically twice inlet bore. SECT 7, SCHD 2G16.10 Water Regs. Warning/overflow pipes should be capable of taking any possible 

flow in the pipe arising from inlet valve failure. See page 8 for side view.

tel 0118 921 9920

         

fax 0118 921 9921

         

[email protected]

         

www.keraflo.co.uk

Warning

tHe float arM Must Be fItteD aBsolutelY 

vertIcallY (In tHe oPen PosItIon) as InDIcateD 

BY tHe sPIrIt level. (see Below)
MIsalIGnMent wIll Prevent tHe valve froM 

closInG. ensure overflow level (B) Is not 

lower tHan 200MM froM tHe centre lIne of  

tHe valve.
tHe warnInG PIPe anD overflow outlet sHoulD 

alwaYs Be aBove tHe HIGHest water level 

acHIeveD Before tHe valve closes.

  ¾”(20)
  1”(25)

  1¼”(32)
  1½”(40)sF

  1½”(40)HF
  2”(50)sF

sizes (dn): 

 

aylesbury kb valve

  

p7

 

dn 

20 

25 

32 

40sF 

40HF 

50sF

 

size 

¾” 

1” 

1¼” 

1½”sF 

1½”HF  

2”sF

  jMin 

175  

175  

175  

175  

210  

210 

 

jMax

 

1800  

1800  

1800  

1800  

1670  

1670 

 

k

  

168  

168  

168  

168  

210  

210 

 

lMax

  

200  

200  

200  

200  

237  

237 

 

M

  

26o  

26o  

26o  

26o  

34o  

34o 

 

nMin

  

160  

160  

160  

160  

180  

180 

 

nMax

  

180  

180  

180  

180  

220  

220 

 

o

  

70  

70  

70  

70  

115  

115 

 

PMin

  

200  

200  

200  

200  

330  

330 

 

PMax

 

1825  

1825  

1825  

1825  

1815  

1815 

 

q

  

65  

65  

65  

65  

120  

120 

 

rMin

  

375  

375  

375  

375  

540  

540 

 

rMax

  

2000  

2000  

2000  

2000  

2000  

2000 

 

sMax

  

215  

215  

215  

215  

268  

268 

 

t

  

26°  

26°  

26°  

26°  

34°  

34° 

 

WMin

  

170  

170  

170  

170  

320  

320 

 

xMax

  

245  

245  

245  

245  

305  

305 

 

yMin

  

500  

500  

500  

500  

800  

800 

a

B

c

D

oPening level (lWl)

xMax

closing level (tWl)

P delayed 

action

y Min 

(tyPically 

requires 

additional 

500MM  

dePtH) 

overFloW

B

c

D

sMax

q

oPen 

Position

oPening 

buoy

e

MiniMuM 

oPening level 

FroM bottoM 

oF tHe tank

WMin

closing 

Float

ø50

oPening 

buoy

closing 

Float

25MM 

Min

Warning PiPe

o

lMax

B

closed 

Position

k

n

j

a

M

sPirit level 

WitH cHain 

disconnected 

bubble Must 

be betWeen 

black lines

r

a

t

P delayed 

action

Summary of Contents for AYLESBURY KB

Page 1: ...T Please keep for future reference PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER TO ANY DIAGRAMS BEFORE INSTALLATION These instructions contain important information which will help you install y...

Page 2: ...as been installed and tested complete and apply the tank label to the tank and send a photograph of the label in place to warranties keraflo co uk in order to receive a full five years extended warran...

Page 3: ...the valves allows sufficient clearance between the float and most internal tank flanges and ribs dimension G shown on drawing on page 7 The valve backnuts may be adjusted to enable fitting to tanks w...

Page 4: ...and retain one backnut 5 Insert the valve tail through the hole in the tank wall replace the backnut with the flanged side against the tank wall 6 Connect the supply pipe then hand tighten the backnut...

Page 5: ...OF THE VALVE 15 The length of this chain determines the opening water level and the position of the float on the chain determines the closing level and the delay 16 CLOSING WATER LEVEL TWL When the ac...

Page 6: ...all of the available chain last link on hanger 21 Applications where the top water level TWL can rise after the valve has closed will cause the chain to become slack A cable tie ratchet strap should...

Page 7: ...vel achieved before the valve closes 20 1 25 1 32 1 40 SF 1 40 HF 2 50 SF SIZES DN AYLESBURY Kb Valve p7 DN 20 25 32 40sF 40HF 50SF SIZE 1 1 1 sF 1 HF 2 SF jmin 175 175 175 175 210 210 jmax 1800 1800...

Page 8: ...0SF SIZE 1 1 1 sF 1 HF 2 SF a 330 330 277 277 277 315 bmax 44 44 55 55 55 92 c 34 34 73 73 73 73 d 19 5 26 9 35 4 35 4 35 4 35 4 e 26 5 33 42 47 5 47 5 6o f 142 142 142 142 186 186 gmin 92 92 74 74 54...

Reviews: