background image

14

HSF (M) 300W 042315

FIGURE 12.  ±PF POWER FAILURE OPTOCOUPLER TIMING DIAGRAM

3.9

LOCAL/REMOTE SENSING

HSF (M and MZ) 300W Power Supplies allow remote error sensing which can compensate up to
0.4 Volts per load wire. Local/Remote error sensing is configured by means of separate DIP
switches mounted on the RA 19-4C Rack Adapter (see RA 19-4C Rack Adapter Operator Man-
ual). Either local or remote sensing MUST be used, otherwise the units will not operate. 

3.10

RETAINING LATCHES

HSF power supplies are provided with (2) retention latches located at each side of the bottom
edge of the front panel (see Figure 5). These latches work in conjunction with the RA 19-4C rack
adapters to prevent unauthorized or inadvertent module extraction from an operating power sys-
tem. The latch is engaged by loosening the cap-head screw approximately 1/2 turn CCW (use 5/
32" hex key) and sliding the latch down to the bottom of the slot, then retightening the cap-head
screw CW until snug. DO NOT OVERTIGHTEN! To release, follow the same procedure, except lift
the latch to the top of the slot. Be sure to move the latch completely up or down to ensure full
engagement and disengagement of the latching mechanism. When the HSF power supply is not
installed in its plug-in rack adapter, it is recommended that the latch be secured in the open (up)
position to prevent damage. 

NOTE: Retaining latches must 

not

 be used to secure the HSF power supply in the rack

adapter for shipping purposes.

4.

LOAD CONNECTION

Connect the load to (+) and (–) terminals at the rear panel of the Rack Adapter (see RA 19-4C
Instruction Manual for details).

5.

CONNECTING MULTIPLE POWER SUPPLIES

All connections to multiple HSF power supplies must be made via the I/O mating connectors at
rear of the Rack Adapter or by the Rack Adapter DIP switches. These connections, including the
configuration of the two internal HSF DIP switches, are described in the Rack Adapter Instruction
manual, and include:

Using one power supply to control the output of multiple supplies.

Using parallel master/slave configurations (for increased current or redundancy) where
the user either predetermines the master or allows the load to determine which is the
master. These configurations also cover the use of the Current Balancing feature of the
HSF power supply. 

Using series configurations (for increased voltage).

Using open-on-fail or close-on-fail alarm schemes with multiple power supplies.

Summary of Contents for HSF 15-22M

Page 1: ...and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without no...

Page 2: ...onnecting Multiple Power Supplies 14 5 1 Adjusting the Voltage 15 5 2 Parallel Connections M Models 15 5 3 Parallel Connections MZ Models 15 5 3 1 Minimum Load 16 5 3 2 Voltage Set Restrictions 16 1 H...

Page 3: ...out this manual where there are differences between M and MZ models refer to the MZ model information for HSF 5 60M The HSF M Models except for HSF 5 60M use the HSF output to power the VDC ON indicat...

Page 4: ...AR 3 8 2 1 AL COM 14 Common contact of alarm relay see PAR 3 8 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one vol...

Page 5: ...02 Unless otherwise noted specifications apply to both M and MZ models 1 M Models only To adjust output voltage down to approximately 0V use external voltage source or resistance see PAR 3 4 2 Refer t...

Page 6: ...ximum Stabilization Source Effect min max 0 1 Typical 0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 3 Typical 2 Maximum default 0 3 Typical 0 6 Maximum see PAR 3 4 Individual Mode 0 100 loa...

Page 7: ...0 RoHS Compliance Contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Emission Radiated Designed to meet FCC Class B VC...

Page 8: ...ront panel reset button to be used to reset the unit after a fault or allow Remote on off via mechanical switch or logic level see PAR 3 4 3 Positions 5 and 6 allows alarm signals to be produced from...

Page 9: ...that overcurrent or overvoltage protection has tripped or thermal overload or fan malfunction has occurred If remote voltage control see PAR 3 4 2 is not enabled the front panel Vadj trimmer see PAR...

Page 10: ...set to A to show output current V indicator Lights green to indicate meter is showing Volts A indicator Lights amber to indicate meter is showing Amperes FIGURE 5 FRONT PANEL CONTROLS INDICATORS AND...

Page 11: ...For M Models except HSF 5 60M only To ensure proper operation of the alarm relay meter and LED indicators do not adjust external voltage below minimum listed in Table 4 Connect the voltage source acro...

Page 12: ...se to reduce output voltage then reset the unit 3 5 REMOTE ON OFF When power is ON at the source the output may be turned ON or OFF using the RC signals if the remote ON OFF feature is enabled Note th...

Page 13: ...e following protection features are implemented in the HSF 300W Series M and MZ Models overvoltage and overtemperature PAR 3 7 1 overcurrent PAR 3 7 2 fan failure PAR 3 7 3 and undervoltage PAR 3 7 4...

Page 14: ...N ALARM indicator can be configured to light red if the respective power supply output voltage is lost or if the POWER switch is set to OFF This is enabled when DIP switch 1 position 8 set to ON This...

Page 15: ...s nor mally conducting When the alarm is activated upon detection of power loss overvoltage fan fault overtemperature or overcurrent condition the transistor cuts off and the collector emitter cir cui...

Page 16: ...up or down to ensure full engagement and disengagement of the latching mechanism When the HSF power supply is not installed in its plug in rack adapter it is recommended that the latch be secured in t...

Page 17: ...LS When using parallel connected M Models a minimum load is required to avoid the slave becom ing idle When the slave is idle the output is off no lights are lit and the alarm is set The mini mum load...

Page 18: ...n redundant mode with load less than 10 per unit For loads less than 10 voltage stabilization may be affected if units are turned off and on via the front panel causing voltage on the paralleled bus t...

Reviews: