background image

4

HSF (M) 600W 042315

TABLE 3.  POWER SUPPLY RATINGS AND SPECIFICATIONS

CHARACTERISTIC

SPECIFICATION

CONDITION/NOTES

Input Voltage

Nominal: 100-120V a-c, 200-240V a-c 
Range: 85-264V a-c

(1)

, 110-370V d-c

0 to 100% load, -10 to 40°C

Input Source Frequency

Nominal: 50-60 Hz
Range: 47-440 Hz

0 to 100% load, -10 to 40°C
At 440 Hz leakage current exceeds
UL/VDE safety spec. limit.

Input Current: (Maximum Load At 
25°C with Nominal Output Voltage)

8.4A rms max.

100 - 120V a-c

4.2A rms max. 

200 - 240V a-c

Switching Frequency

140KHz typ.

Forward Converter

Input Protection

A limiting resistor in series with a resistor fuse (and thyristor circuit) reduces start-up surge. 
The internal power supply is protected against shorts by an input fuse. Fuse value 15.0A at 
250 Volts

Input Surge  cold start, interval > 30 

sec ( First surge only, not including 

current flow into EMI filter )

15A typ., 30A max. first surge

100 - 120V ac

30A typ., 60 max. first surge

200- 240 V ac

Leakage Current: 

0.45mA typ., 0.75mA max. 

120V a-c, 60Hz per IEC 950 and UL1950

0.60mA typ., 0.75mA max. 

240V a-c, 60Hz per IEC 950 and UL1950

Power Factor

0.99 typical

100V a-c, max load, nominal output, 
per EN 61000-3-2

0.95 typical

200V a-c, max load, nominal output
per EN 61000-3-2

Transient Recovery

excursion

characteristic

±4% maximum

50% to 100% load, 
transient time >50

sec

recovery time 1 ms maximum

Stabilization

NOTE: Refer to Table 2, ripple and noise and Note (8) for minimum output voltage required to 

meet stabilization specifications.

Source Effect (min - max) ±0.1% Typical, ±0.2% Maximum

85 to 132V a-c, 170 to 264V a-c

Load Effect ±0.3% Typical, ±0.6% Maximum 

(2)

0%-100% load change

Temperature Effect ±0.5% Typical, ±1.0% Maximum

–10° to 40°C

Combined Effect ±0.9% Typical, ±1.8% Maximum

Source, Load and Temperature

Time Effect 0.2% Typical, 0.5% Maximum

1/2 to 8 hours at 25°C

Start-up Time

280 msec Typical, 350 msec Maximum

100V a-c 

100 msec Typical, 150 msec Maximum

240V a-c

Output Hold-up Time

30 msec Typical, 20 msec Minimum.

100V a-c 

40 msec Typical, 20 msec Minimum.

240V a-c

Overvoltage Protection

When the Power Supply goes into an overvoltage condition, the output is cut OFF. See PAR. 
3.7.1.

Remote Control ON/OFF:

±RC pins control on/off as follows:
 “High”, 2.4V to 24V (or open), unit OFF- Fan Off; 
 “Low”, 0.0V to 0.4V (or closed), unit ON. 
Source current: 1.6mA maximum at low level 
Sink current: 1.0 mA maximum at high level. 

Must be enabled by DIP switch positions 3 
and 4 (see PAR. 3.5).

(1) For input voltage between 85 to 95V a-c maximum operating temperature is 35°C.
(2) MZ Models: ±0.3% Typical, ±2% Maximum (default). When VDC/ALARM ON powered from internal reference voltage: ±0.6% 

Maximum, ±0.3% Typical (see PAR 3.4.3).

Summary of Contents for HSF 12-53M

Page 1: ...del and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change withou...

Page 2: ...le Power Supplies 15 5 1 Adjusting the Voltage 15 5 2 Parallel Connections M Models 16 5 3 Parallel Connections MZ Models 16 5 3 1 Minimum Load 16 5 3 2 Voltage Set Restrictions 16 1 HSF Rear Panel Co...

Page 3: ...tion for hot swap and parallel redundant N 1 operation RoHS compliant models are indicated by HSF e g HSF 28 23M The HSF M Models use the HSF output to power the VDC ON indicator internal alarm relay...

Page 4: ...PAR 3 8 2 1 AL COM 14 Common contact of alarm relay see PAR 3 8 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one v...

Page 5: ...002 0 005 0 01 0 01 0 02 Unless otherwise noted specifications apply to both M and MZ models 1 M Models only To adjust output voltage down to approximately 0V use external voltage source or resistance...

Page 6: ...3 2 Transient Recovery excursion characteristic 4 maximum 50 to 100 load transient time 50 sec recovery time 1 ms maximum Stabilization NOTE Refer to Table 2 ripple and noise and Note 8 for minimum ou...

Page 7: ...1ms 5 msec non operating 1 2 sine pulse three shocks on each axis Power Supply is fixed on its bottom side Safety UL 60950 1 1st Edition 2007 10 31 CSA C22 2 No 60950 1 03 1st Edition 2006 07 EN 60950...

Page 8: ...n external trimpot or voltage source see PAR 3 4 Positions 3 and 4 of SW1 and SW2 either allow the front panel reset button to be used to reset the unit after a fault or allow Remote on off via mechan...

Page 9: ...the POWER switch is set to OFF CAUTION DO NOT repeatedly toggle the power ON OFF switch as this may cause unit to fault NOTE The ON OFF switch must be set to OFF before removing unit from rack adapte...

Page 10: ...c output voltage OUTPUT RESET switch Used to recycle power in the event of an alarm condition see PAR 3 7 Not functional when remote on off control is enabled see PAR 3 5 POWER ON OFF switch Applies p...

Page 11: ...HSF 600W M and MZ Models 3 4 2 REMOTE VOLTAGE CONTROL For remote voltage control set positions 1 2 and 7 for SW1 and SW2 as shown in Figure 6B This removes control from the front panel Vadj control a...

Page 12: ...A Load effect is 1 maximum To use the HSF output voltage to power the VDC ON ALARM indicator set Posi tion 7 of SW1 to OFF and Position 8 of SW2 to ON see Figure 8B Load effect is 0 6 maxi mum however...

Page 13: ...level the sink current is 1 0mA Positions 3 and 4 of both DIP switches must be restored to the factory default setting Figure 9A if remote ON OFF is not used The RC pins are isolated from DC output p...

Page 14: ...he temperature returns to within specifications To restart reset the unit set the POWER ON OFF switch to OFF wait until unit cools then set the POWER switch to ON The power supply cannot be reset usin...

Page 15: ...LARM indicator is enabled to light red the VDC ON ALARM indicator must be powered from the HSF output see PAR 3 4 3 3 8 2 ALARM SIGNALS Either of two options are available for signalling alarms isolat...

Page 16: ...power fail signal The default state of the alarm is logic low The sink current for the optocoupler is 50mA maximum the maximum collector to emitter saturation voltage is 0 40 Volts and the collector...

Page 17: ...purposes 4 LOAD CONNECTION Connect the load to and terminals at the rear panel of the Rack Adapter see RA 19 4C Instruction Manual for details 5 CONNECTING MULTIPLE POWER SUPPLIES All connections to...

Page 18: ...tion 7 as defined below NOTE If the minimum load is maintained voltage set restric tions are not required If position 7 of SW1 is set to off default see PAR 3 1 the VDC ON indicator is powered from th...

Reviews: