KEPCO HSF 12-13PFC Instruction Manual Download Page 3

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102



www.kepcopower.com   



 email: [email protected]

 081721

228-1550 REV 17

3

CONNECTIONS.  

The 24-pin I/O connector is designed

to mate with the corresponding connector in the Series RA
19-(X)B Rack Adapter.

 

(+) SENSE, (–) SENSE: 

These lines are provided to com-

pensate for voltage drops in the load connecting wires. 

The

Sense lines must be connected to their respective (+)
and (–) output terminals

, either at the load or at the rack

adapter (see Rack Adapter Manual). The connection
ensures the most accurate error tracking. Maximum volt-
age drop compensation in the load connecting wires for
each model is calculated as the difference between the
minimum overvoltage (see Table 1 or 2) and the maximum
adjustment range (see Table 1 or 2), divided by two to give
the voltage drop compensation per lead. Higher compen-
sation values are possible if output voltage is decreased
below the maximum adjustment range shown in Table 1 or
2.

NOTE:

The Sense lines must be connected for 

the power supply to work properly!

OUTPUT (+), OUTPUT (–): 

 These lines are the power supply

d-c output lines which are connected to the load.

CURRENT SHARE BUS (CSB): 

 (Not available on 3.3V

model.) Connecting the CSB lines of power supplies oper-
ating in a parallel configuration causes output current to be
shared equally. (See Rack Adapter Manual for additional
information on parallel configurations.). For current sharing
to work properly the outputs of all paralleled units must be
within 250 mV (max) of each other and each unit must be
operating at between 10% to 100% of rated output current.
If current to the load goes below 10% for each unit in cur-
rent share mode, all MASTER ON lights may go on (see
load effect specifications); this indicates that forced current
share is no longer working, units are simply in automatic
current share mode. (If forced current sharing at less than
10% nominal current per supply is needed, contact Kepco
application engineering.) Remote sensing is recom-
mended. For master/slave operation to work properly each
unit should be adjusted to 40 mV (optimum) less than the
next paralleled unit (unit 1 is adjusted to V

OUT

, unit 2 to

V

OUT

 – 40mV, and unit 3 to V

OUT

 – 80mV, etc. If the master

fails, the unit 2 will become the new master). The 40 mV
difference can be reduced to a minimum of 25 mV as
needed to parallel many units and still keep all units within

250 mV of each other. Adjust the outputs using Vadj trim-
mer on front panel. 

• Optimum difference among output voltages of par-

alleled units: 40mV

• Maximum difference among output voltages of 

paralleled units: 250 mV

• Minimum difference among output voltages of par-

alleled units: 25 mV

ALARM: 

 The Alarm NC (normally closed) - Open on Fail-

ure and Alarm NO (normally open) - Close on Failure lines
are relay contacts referenced to Alarm Common. If the unit
fails, the path between Alarm NC - Open on Failure and
Alarm Common opens, the path between Alarm NO - Close
on Fail and Alarm Common is a short circuit. Figure 3 illus-
trates typical Close on Fail and Open on Fail circuits to give
a failure indication if any one of a number of power supplies
fail.

INPUT POWER: 

Line (either a-c or d-c source power), Neu-

tral and Ground (chassis)

FIGURE 3.  TYPICAL ALARM CIRCUIT DIAGRAMS

Summary of Contents for HSF 12-13PFC

Page 1: ...page 4 standard models and Section IV on page 6 suffix C T X and Y OPTIONS Options are identified by suffix T PFCT offers improved efficiency and less weight C PFCC offers current monitoring via an integral current sensing resistor includes option T X PFCX offers remote on off includes option T and Y PFCY includes options C X and T II FEATURES FRONT PANEL ACCESS The front panel provides a power ON...

Page 2: ...line ac input line failure etc results in an alarm All models include an isolated internal relay offering nor mally closed and normally open contacts referenced to an isolated common These contacts are rated for 1A at 30V d c and 0 5A at 125V a c These contacts may be used to configure close on failure or open on failure alarm cir cuits see Figure 3 for typical alarm circuits Refer to the applicab...

Page 3: ... each other and each unit must be operating at between 10 to 100 of rated output current If current to the load goes below 10 for each unit in cur rent share mode all MASTER ON lights may go on see load effect specifications this indicates that forced current share is no longer working units are simply in automatic current share mode If forced current sharing at less than 10 nominal current per su...

Page 4: ... 265V a c Load Effect 10 100 load change 0 5 typ 1 5 max except 3 3V model 1 typ 2 max Temperature Effect Range 10o to 71o C 0 5 typ 1 0 max Combined Effect includes source load and temperature effects 0 9 typ 1 8 max except 3 3V model 1 typ 2 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max TABLE 1 OUTPUT RATINGS AND SPECIFICATIONS HSF PFC 150W SERIES STANDARD NO SUFFIX MODEL HSF 3 3 30PFC HS...

Page 5: ...ient 10 to 85 relative humidity 100 Megohms min LEAKAGE CURRENT Per IEC 950 and UL 1950 0 23 mA typ 0 35 mA max 120V a c 60Hz 0 45 mA typ 0 7 mA max 240V a c 60Hz SAFETY All units designed to meet EN 60950 U S UL 60950 3rd Ed Canada CAN CSA 22 2 No 60950 00 3rd Ed ambient temp 50 C 150W units are CE marked per the Low Voltage Directive LVD EN60950 The standards do not apply with DC input operation...

Page 6: ...2 PFCC PFCT PFCX PFCY HSF 15 10 PFCC PFCT PFCX PFCY HSF 24 6 3 PFCC PFCT PFCX PFCY HSF 28 5 3 PFCC PFCT PFCX PFCY HSF48 3 1 PFCC PFCT PFCX PFCY OUTPUT VOLTS d c NOMINAL 3 3V 5V 12V 15V 24V 28V 48V ADJUSTMENT RANGE 2 8 3 4V 4 3 5 3V 9 8 13 0V 12 8 16 3V 19 2 26 0V 23 0 30 2V 40 0 52 2 OVERVOLTAGE SETTING 1 2 3 4 4 6V 5 2 6 5V 13 2 15 2V 16 8 18 8V 26 5 30 3V 31 5 34 8V 54 5 59 8V OUTPUT CURRENT NOM...

Page 7: ...00V a c for one minute Between input and case ground 2KV a c for one minute INSULATION RESISTANCE Between input and ground output and ground input and output 500V d c 15 to 35 C ambient 10 to 85 relative humidity 100 Megohms min LEAKAGE CURRENT Per IEC 950 and UL 1950 0 29 mA typ 0 45 mA max 120V a c 60Hz 0 40 mA typ 0 65 mA max 240V a c 60Hz SAFETY All units designed to meet EN 60950 2001 U S UL ...

Page 8: ...o fault When output voltage is available the green VDC ON LED is on While monitoring output voltage at the front panel test points the Output Voltage Adjust trimmer allows adjustment of the output voltage FIGURE 5 COMPONENT LOCATIONS Master slave parallel configurations of one or more power supplies are covered in the applicable RA 19 X B Rack Adapter manual The MASTER ON LED amber goes on under a...

Page 9: ...ANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 081721 228 1550 REV 17 9 FIGURE 6 HSF PFC 150W INCLUDING SUFFIX C T X AND Y POWER SUPPLY OUTLINE DRAWING ...

Reviews: