background image

6

228-1678 REV 1

 081415

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102



http://www.kepcopower.com   



 email: [email protected]

IV — OPERATION     

Turn the unit on using the front panel POWER switch/cir-
cuit breaker (see Figure 2 or 3). 

CAUTION: DO NOT

repeatedly toggle the POWER on/off switch as this
may cause unit to fault.

 If actuator does not lock when

released, wait a few seconds before trying again. The cir-
cuit breaker is “trip-free;” if overload exists, contacts can-
not be held closed by actuator.

NOTE: PC 15 rear programming connector must be

installed to enable local control of the unit.

NOTE: BOP 5-20DL only: apply voltage (+3.5 to +24V)

to pin 2 referenced to pin 3 of ON-OFF PORT
at rear panel to enable the output. 

4.1.  VOLTAGE MODE OPERATION WITH CUR-

RENT LIMITING.  

The BOP may be used as a stabi-

lized (d-c) source of positive or negative voltage with out-
put current limiting (for either polarity) when pre-selected
for the application at hand. Always monitor the front panel
meters while adjusting output voltage/current.

1. Determine the output voltage and current requirements

of your load. Disconnect the load and set the BOP
MODE switch to CURRENT and the CURRENT CON-
TROL switch to ON.

2. Voltage limits are recommended to be greater than the

maximum voltage required for the load by 10% of the
rated voltage of the unit (e.g., for a 72V BOP and a
load that requires 30V, set voltage limits to ±37.2V).

If specific ± voltage limits are not needed, use a screw-
driver to adjust the 

+

V

 VOLTAGE LIMIT potentiome-

ter to full clockwise position and 

V

 VOLTAGE LIMIT

potentiometer to full counterclockwise position.

If specific ± voltage limits are needed, proceed as fol-
lows. 

a. Turn CURRENT CONTROL fully counterclockwise.

Use a screwdriver to adjust the 

V

 VOLTAGE

LIMIT potentiometer as desired (recommended to
be 10% greater than the maximum negative volt-
age required for the load), monitoring the VOLT-
AGE meter for the correct limiting value. 

b. Turn CURRENT CONTROL fully clockwise. Use a

screwdriver to adjust the 

+

V

 VOLTAGE LIMIT

potentiometer as desired, monitoring the VOLTAGE
meter for the correct limiting value. 

3. With the a-c POWER circuit breaker/switch set to OFF,

connect a short circuit across the OUTPUT and COM-
MON terminals. 

4. Set the CURRENT CONTROL switch to OFF. Set the

MODE switch to VOLTAGE and the VOLTAGE CON-
TROL switch to ON, then set BOP POWER a-c circuit
breaker/switch to ON.

5. Adjust the 

+

I

 and

 

I

 CURRENT LIMIT potentiome-

ters for both polarities as required, monitoring the
CURRENT meter for the correct limiting value. Pro-
ceed as follows: 

a. Turn VOLTAGE CONTROL fully counterclockwise.

Use a screwdriver to adjust the 

I

 CURRENT

LIMIT potentiometer as desired. 

b. Turn VOLTAGE CONTROL fully clockwise. Use a

screwdriver to adjust the 

+

I

 CURRENT LIMIT

potentiometer as desired. 

c. Set a-c POWER circuit breaker/switch to OFF, then

remove the short circuit from the output.

d. Set a-c POWER circuit breaker/switch to ON and

adjust the output voltage to zero using the VOLT-
AGE CONTROL.

e. Set a-c POWER circuit breaker/switch to OFF, then

connect the load to the BOP output.

6. Set a-c POWER switch/circuit breaker to ON, and

adjust the operating voltage by means of the VOLT-
AGE CONTROL to the value required.

NOTE: If the output current exceeds the pre-adjusted
value at any time the VOLTAGE MODE indicator will go
out and the CURRENT LIMIT indicator will go on. After the
cause of the overcurrent is eliminated, the indicator lights
will return to their initial status.

4.2.  CURRENT MODE OPERATION WITH VOLT-

AGE LIMITING. 

The BOP may be used as a stabilized

d-c source of positive or negative current, with output volt-
age limiting (for either polarity), pre-selected for the appli-
cation at hand. Always monitor the front panel meters
while adjusting output voltage/current

Summary of Contents for BOP 100W

Page 1: ...s it can act as either a source output voltage is the same direction as output current or a sink output voltage is opposite that of output current An example is shown in Figure 1 where the BOP is prog...

Page 2: ...service 3 2 PRELIMINARY CHECKOUT A simple oper ating check after unpacking and before permanent instal lation is advisable to ascertain whether the BOP has suffered damage in shipment 1 Install PC15...

Page 3: ...reduces noise ripple that may be present at the output REMOTE SENSE CONNECTIONS Remote sensing con necting the corresponding SENSE terminals to the OUT PUT and COMMON terminations at the load instead...

Page 4: ...NUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 2 BOP FULL RACK FRONT PANEL CONTROLS INDICATORS AND TERMINATIONS FIGURE 3 BOP 3 4 R...

Page 5: ...L OPENINGS AND THE TOP OF THE CASE MUST BE KEPT CLEAR FROM ALL OBSTRUCTIONS TO ENSURE AIR CIRCU LATION Periodic cleaning of the interior of the power sup ply is recommended If the BOP is rack mounted...

Page 6: ...ter as desired recommended to be 10 greater than the maximum negative volt age required for the load monitoring the VOLT AGE meter for the correct limiting value b Turn CURRENT CONTROL fully clockwise...

Page 7: ...d monitoring the CURRENT meter for the correct limiting value c Set the VOLTAGE CONTROL switch to OFF Set a c POWER switch circuit breaker to OFF then remove the short circuit from the output but leav...

Page 8: ...8 228 1678 REV 1 081415 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com...

Reviews: