KEPCO ATE-DMG Quick Start Manual Download Page 3

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102



http://www.kepcopower.com   



 email: [email protected]

 020316

228-1768

3

c. Overcurrent and Overvoltage protection are set to

the maximum values (see Operator Manual, PAR.
1.1), but are not displayed.

NOTE: Six keys with dual functions are labeled with both a

command and a number. The command label is
referred to when the unit is in   command entry
status; the number is referred to when the unit is
in 

 

data entry status.

4. Press 

OUTPUT ON/OFF

 key to enable the output. 

5. Connect a digital voltmeter (DVM) to the (+) and (–) ter-

minals at the rear panel and verify DVM reads 0V.

6. Press 

V SET

 key. Verify bottom line of LCD reads 

Vset

 nn

 (where nn = voltage setting).

7. Use number keys to enter rated maximum voltage (e.g.

for ATE 25-40DMG, 25V is the rated maximum voltage)
and press 

ENTER

. Output voltage will be displayed at

bottom left of LCD. 

8. Use 

 and 

 keys as necessary to adjust output pre-

cisely to rated maximum voltage. Verify DVM voltage
reading agrees with displayed voltage on LCD within
0.01% of rated maximum. If the LCD reads 

VsetMAX=

(value)

, you are entering a value higher than the

maximum voltage setting.

3.3.  INSTALLING THE POWER SUPPLY.  

 ATE-

DMG is intended to be rack-mounted; the four bottom feet
must be removed prior to installation. Refer to PAR. 3.5 for
cooling requirements.

3.4.  CONNECTIONS. 

Connections are made using the

rear panel terminations (see Figure 4).

3.4.1.  LOAD CONNECTION, GENERAL. 

 Connect the

load between –OUT and +OUT output terminals at the rear
panel (see Figure 4. 

Sense connections are required,

either local or remote, must be used; otherwise the
unit will not operate. 

See PAR. 3.4.2 for local sensing, see PAR. 3.4.3 for
remote sensing. “Fast” mode is recommended if step
changes in the load are expected: if, for example, the load
is rapidly changing in value, or if the power supply is pro-
grammed with step functions (square wave, pulse, etc.)
and maximum dynamic performance is expected. Set the
unit to “fast” mode by referring to the full Operator Manual
(see PAR. 1.1). Note that ripple in “fast” mode will be higher
than for the default “slow” mode.

Terminals on the barrier strip permit maximum flexibility in
power supply/load interface techniques. The unit is shipped
with several jumper links installed (see Figure 3) for the
default configuration: front panel (local) control of output
voltage, output current and VP crowbar level with the
power supply operating in the “slow” mode. Links on the
barrier strip must be tightened. 

CAUTION: Loose links at

the barrier strip will cause malfunction of the power
supply. 

To configure the unit to allow remote programming of the
power supply or for “fast mode,” refer to the full Operator
Manual (see PAR. 1.1). 

3.4.2.  LOAD CONNECTION, LOCAL SENSING.  

Figure

3 illustrates load connection using local sensing. Refer to
the full Operator Manual (see PAR. 1.1) for load wire selec-
tion guidelines. The output power leads should be twisted
or tied together to reduce EMI. 

FIGURE 3.  LOCAL SENSING

3.4.3.  LOAD CONNECTION, REMOTE SENSING.  

 To

avoid excessive output effects at remote loads, remote
error sensing must be used (Kelvin connection). A pair of
wires (twisted to reduce EMI) connected from the sensing
terminals directly to the load will compensate for load wire
voltage drops up to 0.5 volt per wire (refer to Figure 4.
Observe polarities: the negative sensing wire must go to
the negative load wire, and the positive sensing wire goes
to the positive load wire. 

If step changes in the load are expected (e.g., the load is
rapidly changing in value and maximum dynamic perfor-
mance is expected directly at the load terminals, refer to
the full Operator Manual (see PAR. 1.1) for alternative
remote sensing connections.

For large capacitive loads with long wire runs, refer to the
full Operator Manual (see PAR. 1.1) for techniques used to
reduce low frequency oscillations observed at the load.

Summary of Contents for ATE-DMG

Page 1: ...modes Slow mode operation is recommended for applications demanding a constant volt age source Fast mode operation is best if the output volt age must change rapidly either in response to an external...

Page 2: ...test is successful the following indica tions are visible a The alphanumeric display LCD indicates the model and GPIB address b After approximately 2 seconds the display changes to the power on defaul...

Page 3: ...ue or if the power supply is pro grammed with step functions square wave pulse etc and maximum dynamic performance is expected Set the unit to fast mode by referring to the full Operator Manual see PA...

Page 4: ...t voltage that can be supported between either output terminals and chassis ground is 500V d c or peak Either side of the output may be grounded A resistor capacitor network is connected from the nega...

Page 5: ...press ENTER 3 Depress the DISABLE button and keep it depressed white turning the LEVEL control counterclockwise until the CROWBAR indicator energizes simulated crowbar action 4 With the DISABLE butto...

Page 6: ...to accept dis played value I SET Command Entry active Press to set output current After I SET is pressed previous setting is displayed Data entry required to enter new value of output current press E...

Page 7: ...Command Entry active In CV constant voltage press to increase output volt age by increment equal to voltage resolution 0 025 of EOmax In CC constant current press to increase output cur rent by increm...

Page 8: ...he key is pressed Press ENTER or CLEAR to exit without changing setting Enter new value the key erases data just entered and press ENTER to accept new setting or CLEAR to exit without changing setting...

Reviews: