![KEP BATCHtrol II Installing & Operating Manual Download Page 39](http://html1.mh-extra.com/html/kep/batchtrol-ii/batchtrol-ii_installing-and-operating-manual_1956282039.webp)
35
6-1 Warning Messages
6-1 Warning Messages (continued)
6-1.5 BAD FREQ
Indicates that the values in the 16 Point setup
are not acceptable. This condition will occur
when the frequency values are not in ascending
order. The display will continue to display this
message until the error is corrected. To correct
the error see Section 3-3, Setup Procedure.
6-1.6 SECURITY
Indicates that no signal has come in for the dura-
tion time set in the Lockout menu. Lockout code
must be entered before the unit will continue.
Section 3-3, Setup Procedure.
6-2 Troubleshooting
6-2 Troubleshooting
6-2.1 General
The following troubleshooting procedures have
been developed as an aid in locating defects.
Not every possible problem has been listed,
but a general isolation procedure for tracking
down problems has been given. A standard
recommendation is the removal of power for 2
seconds. This allows the microprocessor to go
through a reinitialization cycle at power up. If
it is determined that the unit is faulty, contact
your local Factory Representative or Sales Of-
fi ce concerning replacement. The Batcher is
not fi eld serviceable and all repairs should be
performed by the factory.
6-2.2 Problems
Symptom:
Display will not light.
Possible Cause: No power to unit, power to unit
not to specifi cations or bad connection between
display board and mother board.
Test Procedure: See Specifi cations Section 1-4
for proper input voltages. Then;
a)
Check AC voltage input on terminals 17 &
18.
b)
(if DC Powered unit) Check DC voltage input
on terminals 12 & 14.
c)
Check connection of display board to mother
board
Corrective Action:
If all checks okay, replace
Corrective Action:
Corrective Action:
unit.
6-2.2 Problems
Symptom:
Unable to start batch.
Possible Cause #1: Displayed Batch count al-
ready exceeds the Preset value.
Test Procedure: Check Preset value against
the displayed value. If the Preset is less, go to
corrective action.
Corrective Action:
Reset the unit by press-
Corrective Action:
Corrective Action:
ing the CLR button or change the Preset to a
larger value.
Possible Cause #2: Incorrect programming.
Test Procedure: Check for programming er-
rors, review manual.
Corrective Action:
Reprogram unit as re-
quired.
Possible Cause #3: Defective Circuit board or
component.
Test Procedure: Press the Start button and
check for relay action. An OHM meter across
the appropriate relay terminals should give
the proper indication. (Be sure to disconnect
all power to the relay terminals fi rst!)
Corrective Action:
If no relay action replace
Corrective Action:
Corrective Action:
unit.
Symptom:
Unit not totalizing.
Possible Cause #1: Incorrect programming.
Test Procedure: Check for programming er-
rors, review manual. For Example, if the K
Factor is too large it may take some time be-
fore a count is registered on the display.
Corrective Action:
Reprogram unit as re-
Corrective Action:
Corrective Action:
quired.
Possible Cause #2: Input signal invalid.
Test Procedure: See Specifi cations Section
1-4 for proper input signals. Then use oscil-
loscope to;
a)
Check Analog input on terminals 3 and
12 for proper current or voltage levels.
b)
(if Digital unit) Check Digital voltage in-
put on terminals 3 and 12.
Corrective Action:
If inputs check okay, re-
Corrective Action:
Corrective Action:
place unit.