10.5.4.8. Configuration - Network
These are the network settings of the PowerManager. The device is delivered with a standard configuration.
Default IP Address:
192.168.100.224
Subnet-Mask:
255.255.255.0
User / password:
admin / password
This data can be adapted after commissioning for your own environment.
IPv4 address, subnet mask, gateway
Network configuration of the PowerManager. You can enable DHCP for IP configuration. In this case, the
PowerManager must always be assigned the same IP address from the DHCP server. The MAC address of the
device can be read here. Alternatively, manual network data can be specified.
DNS server address 1 / 2 (Domain name server address)
Depending on the network configuration, e.g. if using an ADSL router, this may also be the gateway address.
Public DNS Server: 8.8.8.8 or 8.8.8.4
10.5.4.9. Configuration - Communication
E-mail Settings
In order for the PowerManager to be able to send e-mails to the configured users (for example, if the threshold
is exceeded), an e-mail server (SMTP or ESMTP) must be configured here. If you have configured a DNS
server in the DNS settings, you can use the DNS name of the e-mail server here. By using ESMTP, you can
enter the e-mail credentials provided by your e-mail provider. In addition - depending on the mail server - an
encryption with an associated port must be selected.
When selecting an encryption type (STARTTLS / SSL), the corresponding standard port is automatically entered
as well. If required, it can be changed to any port.
Note that many mail servers require existing sender addresses for proper mail delivery.
E-mail signature
Enter a signature that will be sent with each e-mail. The signature is limited to a length of 1000 characters.
SNMP settings
The PowerManager supports SNMP V2 to query the readings of all connected SmartMeters.
For this a MIB (Management Information Base) is available. Alarms can also be sent in the form of SNMP traps
to up to 2 hosts. To do this, enter the destination IP addresses for the hosts and the corresponding
communication port (default: 162).
For queries, a name must additionally be entered in the field "Public Community".
The changes to the network settings are directly active after saving.
Page
(07-2018, subject to change)
kentix.com
100
Sm
a
rt
Me
te
ri
n
g