SAFETY INTERLOCK ACCESS CONTROL SYSTEM
7
Control Panel Static Checks
4-44. The key switch and push-buttons are not damaged and operate smoothly.
4-45. The external power supply (wall transformer) is connected to the PCB.
4-46. The screws to any terminal blocks that have wires connected to them are tight and the wires won’t pull out
with moderate pulling force.
4-47. Ensure the bypass jumpers are removed for each of the “Safety Loop Inputs” that have wires connected to
them (in use).
4-48. Ensure the bypass jumpers are in place for each of the “Safety Loop Inputs” that do not have wires connected to
them (not used).
4-49. Ensure the +12V jumpers are removed from any magnetic lock that is connected to an external power source.
4-50. Ensure the ’EXIT NOW AUTO RESET’ jumper is installed unless the customer has specified that closing the doors
should not terminate the exit now chime. Select the status of the jumper: installed/not installed.
Safety Loop Checks
4-51. The ‘ENTRYWAY CLOSED’ LED illuminates when all the doors are closed and extinguishes when any door
is opened.
4-52. The front panel ‘SYSTEM READY’ LED illuminates when all the doors are closed and all the ‘E-STOP’ and
‘E-ACCESS’
push-buttons are not pressed.
4-53. The front panel ‘SYSTEM READY’ LED extinguishes when any of the doors are open or ‘E-STOP’ or ‘E-ACCESS’
buttons are pressed.
4-54. With the ‘SYSTEM READY’ LED not illuminated, pressing the front panel ‘START’ button does not engage
the system.
4-55. With the ‘SYSTEM READY’ LED illuminated, pressing the front panel ‘START’ button engages the system.
4-56. With the system engaged, press the front panel ‘EMERGENCY STOP’ button and make sure the system
disengages.
4-57. With the system engaged, press any external ‘E-STOP’ or ‘E-ACCESS’ buttons to ensure the system disengages.
Remote Inputs
4-58. When the ‘REMOTE START’ button (if so equipped) is pressed the ‘START PB’ LED on PCB-EG001 adjacent to
TB12 illuminates and extinguishes when the button is released.
4-59. When the remote ‘ENTER/EXIT REQUEST’ pushbutton (if so equipped) is pressed the ‘EXIT REQ’ LED on the
PCB-EG001 adjacent to TB11 illuminates and extinguishes when the button is released.
4-60. When any keypad (if so equipped) is actuated the ‘EXIT REQ’ LED on PCB-EG001 adjacent to TB11 illuminates
for approximately one second.
Exit Request Function
4-61. With the system engaged pressing any ‘ENTER/EXIT REQUEST’ pushbutton or activating a correct keypad code
results in the system entering into exit now mode. The audible exit chime shall sound for a preset time of 5 to
120 seconds.
4-62. With the system in exit now mode and the ‘EXIT NOW AUTO RESET’ jumper in place, opening and closing a door
contact terminates exit now mode.
4-63. With the system in exit now mode and the ‘EXIT NOW AUTO RESET’ jumper not in place, opening and closing a
door will not terminate exit now mode.
Summary of Contents for Entry-Guard
Page 1: ...OPERATION MANUAL SAFETY INTERLOCK ACCESS CONTROL SYSTEM...
Page 11: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 11 Section 10 1 APPLICATION LAYOUT OPTIONS...
Page 12: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 12 Section 10 2 CONTROL PANEL FACEPLATE...
Page 13: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 13 Section 10 3 PRINTED CIRCUIT BOARD PCB EG001...
Page 14: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 14 Section 10 4 PRINTED CIRCUIT BOARD PCB EG001 LAYOUT...
Page 15: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 15 Section 10 5 PRINTED CIRCUIT BOARD PCB EG MPI...
Page 16: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 16 Section 10 6 PRINTED CIRCUIT BOARD PCB EG MPI LAYOUT...
Page 17: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 17 Section 10 7 REMOTE START WIRING...
Page 18: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 18 Section 10 8 ACCESS CONTROL WIRING...
Page 19: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 19 Section 10 9 EMERGENCY ACCESS WIRING...
Page 20: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 20 Section 10 10 EMERGENCY STOP WIRING...
Page 21: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 21 Section 10 11 DOOR INTERLOCK WIRING...
Page 22: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 22 Section 10 12 KEYPAD WIRING...
Page 23: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 23 Section 10 13 MAGNETIC LOCK WIRING...
Page 24: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 24 Section 10 14 SINGLE STATUS SIGN WIRING...
Page 25: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 25 Section 10 15 DUAL STATUS SIGN WIRING...
Page 26: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 26 Section 10 16 TRIPLE STATUS SIGN WIRING...
Page 27: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 27 Section 10 17 PCB SIGN WIRING...
Page 28: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 28 Section 10 18 BYPASS KEY SWITCH WIRING...