15. Configuring the panel
15.1 Detection part
Sigma XT+ control panels consist of 2 parts. The detection part has 2, 4 or 8 detection zones and has a number of
configuration options which can be set at the time of commissioning to suit the requirements of the installation.
These options are normally set once and will rarely need to change. The configuration options are only available at
access level 3 which is accessed by operating the Write enable switch to the left as shown below. When the panel
is at access level 3, the buzzer will “pip” three times every few seconds as an indication that it is at this access
level.
Configuration options are simple to enter using the codes the table below. When the control panel is at access
level 3, the sub-text of the Mode and Select buttons is used to enter a number using tens (+10) and units (+1).
When the required code number is displayed, pressing the enter button will cause the dot on the units seven
segment display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8,
C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
Access level 3 (Write enable) enable switch location – slide gently to the right to enable
DOT
FLASHING
NO DOT
ZONE 1 I.S. BARRIER
OPTION SET
ZONE 1 I.S. BARRIER
OPTION NOT SET
Example display showing option set and not set
.