C21* DISABLE
FIRE
BUZZER
C22* DISABLE
FIRE
OUTPUT
C23
DISABLE FAULT OUTPUT
C24
DISABLE EARTH FAULT MONITORING
C25
PULSE R0V OUTPUT
C26
REMOVE AUX 24V ON SYSTEM RESET
C27
INDICATE EXTING RELEASED WHEN EXTING OUTPUT
IS ACTIVE
C28
NO ACTIVATION DELAY UPON MANUAL RELEASE
C29
EXTINGUISHANT OUTPUT CAN BE RESET DURING
IMMINENT PHASE
C2A
LOCAL FIRE RELAY OPERATES UPON RELEASED
SIGNAL
C2b*
EXTINGUISHING OUPUT ON TILL RESET
C2C
LOW PRESSURE SWITCH NORMALLY CLOSED
C2d
DELAY MAINS FALI INDICATION BY 30 MINUTES
C31
ZONE 1 ALARM FROM DETECTOR DELAYED
C32
ZONE 2 ALARM FROM DETECTOR DELAYED
C33
ZONE 3 ALARM FROM DETECTOR DELAYED
C41
ZONE 1 ALARM FROM CALL POINT DELAYED
C42
ZONE 2 ALARM FROM CALL POINT DELAYED
C43
ZONE 3 ALARM FROM CALL POINT DELAYED
C61
ZONE 1 OPERATES THROUGH I.S. BARRIER
C62
ZONE 2 OPERATES THROUGH I.S. BARRIER
C63
ZONE 3 OPERATES THROUGH I.S. BARRIER
C71*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
C72*
ZONE 2 SHORT CIRCUIT INDICATES ALARM
C73*
ZONE 3 SHORT CIRCUIT INDICATES ALARM
C81* ZONE
1
NON-LATCHING
C82* ZONE
2
NON-LATCHING
C83* ZONE
3
NON-LATCHING
CA1
Z1 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
CA2
Z2 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
CA3
Z3 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
E00
PANEL CAN BE RESET IMMEDIATELY DISCHARGE
OUTPUT HAS OPERATED
E01
TO
E29
PANEL CAN BE RESET 1 MINUTE TO 29 MINUTES
AFTER DISCHARGE OUTPUT HAS OPERATED
E30
PANEL CAN BE RESET 30 MINUTES AFTER
DISCHARGE OUTPUT HAS OPERATED
-00
NO EXTINGUISHANT DELAY
-05
5 SECONDS EXTINGUISHANT DELAY
-10
TO
-55
INCREMENT EXTINGUISHANT DELAY IN FIVE
SECOND STEPS
-60
60 SECONDS EXTINGUISHANT DELAY
060
EXTINGUISHANT DURATION TIME IN SECONDS
060
TO
295
INCREMENT EXTINGUISHANT DURATION IN FIVE
SECOND STEPS
300
EXTINGUISHANT DURATION TIME IN SECONDS
NOTE: Setting the option C15 marked with asterisks does not comply with EN12094-1