10.5 Electrical  connections 

Caution: 

Electrical connection of the unit must be carried out by qualified personnel in compliance with the regulations in 
effect in the country where the unit is installed. The company shall not be held liable for damage to persons or 
property caused by incorrect electrical connection. 
The power cord type designation is H05RN-R or above/H07RN-F. 
This appliance can be operated by children aged from 8 years and above and persons with reduced physical 
sensory or mental capabilities or lack of experience and knowledge, if they have been given supervision or 
instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall 
not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. 
The appliance shall be installed in accordance with national wiring regulations. 

Danger! 

Always install a general automatic switch in a protected area near the appliance with an adequate capacity 
characteristic delayed curve with sufficient breaking power. There should be a minimum distance of 3mm 
between the contacts. Earth connection is compulsory by law to ensure user safety while the machine is in 
use. 
Air flow 

255-1530 m3/h 

Power supply voltage 

220-240V 

Power supply phase 

1 phase 

Power supply frequency 

50Hz 

Circuit breaker / Fuse 

15A / 15A 

Wiring  

 

See product wiring nameplate. 

 

Check that the voltage and the frequency of the power supply correspond to 220-240V single phase at 
50Hz;that the available power is sufficient for the running the equipment; and that the supply cables are of 
adequate section for the maximum current which will be required. 

 

Make sure that the power supply system complies with current national safety regulations.   

 

Electrical connections must be made in accordance with the wiring diagrams supplied with the machine. 
For connection to the power supply network, use double-insulated flexible cable, twin pole + earth, section 
1.5mm2, type H05RN-F. 

 

Pass the power supply cable through the slot beside the air filter. Use the cable clamp provided on the 
inner side of the panel to secure the power supply cable and the connecting cables, and strip only the 
length of cable needed to go into the connector block. In the event that the unit is mounted on a metal 
surface, earth connections must be made in compliance with local regulations. If the optional extra electric 
heating element is fitted, a separate power supply must be provided. Use double-insulated flexible cable, 
twin pole + earth, section 2.5mm2, type H05RN-F. 

Startup instructions 

Caution: 

Machine commissioning or the first startup must be carried out by skilled personnel qualified to work on this 
type of product. 
Before starting up, make sure that the installation and electrical connections have been carried out in 
accordance with the instructions in this manual. Also make sure that there are no unauthorized persons in the 
vicinity of the machine during these operations. 

Pipeline system has been vacuumed before initial start the equipment. 

1.  Remove the connecting pipe’s side cover panel by cross screwdriver.     
2.  Remove the bolts that showed at the figure by slotted screwdriver. Start up the pump to circulate the 

Summary of Contents for KFHD12H0EN1

Page 1: ...unit Ceiling Floor type Models KFHD12H0EN1 KFHD20H0EN1 KFHD25H0EN1 KFHD30H0EN1 KFHD38H0EN1 KFHD48H0EN1 KFHD57H0EN1 KFHD65H0EN1 KFHD78H0EN1 KFHE12H0EN1 KFHE20H0EN1 KFHE25H0EN1 KFHE30H0EN1 KFHE38H0EN1 K...

Page 2: ...Ceiling Floor Fan Coil Units 1 Features 3 2 External Appearance 3 3 Products Lineup 4 4 Specifications 5 5 Dimensions 7 6 Service Spaces 9 7 Wiring Diagrams 10 8 Capacity Tables 11 9 Installation 22...

Page 3: ...llation designed for horizontal vertical concealed cabinet application Ceiling Installation Floor Installation Concealed Installation Air return form side or below for flexible choice Movable louver m...

Page 4: ...oducts Lineup Model Air volume CFM Power supply KFHE KFHD12H0EN1 150 220 240V 1Ph 50Hz KFHE KFHD20H0EN1 250 KFHE KFHD25H0EN1 300 KFHE KFHD30H0EN1 400 KFHE KFHD38H0EN1 450 KFHE KFHD48H0EN1 500 KFHE KFH...

Page 5: ...27 24 33 30 28 35 32 30 37 34 32 Fan motor Type Low noise 3 speed fan motor Quantity 1 Fan Type Centrifugal forward curved Blades Quantity 1 2 Coil Row 3 2 Max working pressure MPa 1 6 Diameter mm 9 5...

Page 6: ...4 41 39 46 43 40 48 45 42 H5 H M L dB A 39 36 34 41 38 36 42 39 37 44 41 38 46 43 40 Fan motor Type Low noise 3 speed fan motor Quantity 1 Fan Type Centrifugal forward curved Blades Quantity 2 3 Coil...

Page 7: ...Size 150 250 300 400 450 500 600 800 900 A 800 800 1000 1000 1200 1200 1500 1500 1500 B 584 584 784 784 984 984 1284 1284 1284 C 500 500 700 700 900 900 1200 1200 1200 D 526 526 726 726 926 926 1226...

Page 8: ...ns unit mm Size 150 250 300 400 450 500 600 800 900 A 550 550 750 750 950 950 1250 1250 1250 B 526 526 726 726 926 926 1226 1226 1226 C 500 500 700 700 900 900 1200 1200 1200 D 532 532 732 732 932 932...

Page 9: ...KFHD KFHE Ceiling Floor type General Information 9 6 Service Spaces Cased type a mm 150 b mm 20 Uncased type a mm 200 b mm 80 a a b a a a a b b a a...

Page 10: ...KFHD KFHE Ceiling Floor type 10 General Information 7 Wiring Diagrams...

Page 11: ...0 7 0 96 0 66 0 12 6 5 0 83 0 76 0 1 4 9 0 93 0 71 0 11 6 1 1 02 0 65 0 13 7 3 1 09 0 61 0 13 8 4 9 3 1 12 0 74 0 32 48 1 0 98 0 83 0 28 37 2 1 09 0 77 0 31 45 4 1 18 0 73 0 34 53 5 1 26 0 69 0 36 60...

Page 12: ...2 1 2 0 52 26 5 1 6 1 35 0 46 20 5 1 77 1 26 0 51 25 1 1 92 1 18 0 55 29 5 2 04 1 12 0 59 33 5 4 1 72 1 15 0 37 13 3 1 51 1 31 0 32 10 2 1 66 1 22 0 36 12 5 1 81 1 15 0 39 14 8 1 94 1 08 0 42 16 9 5 1...

Page 13: ...1 62 0 71 37 3 2 16 1 83 0 62 28 9 2 39 1 7 0 69 35 2 2 6 1 6 0 74 41 5 2 76 1 51 0 79 47 1 4 2 32 1 56 0 5 18 7 2 04 1 78 0 44 14 4 2 25 1 65 0 48 17 6 2 45 1 55 0 53 20 7 2 62 1 46 0 56 23 8 5 2 2 1...

Page 14: ...0 91 69 1 2 80 2 37 0 80 53 5 3 09 2 20 0 89 65 3 3 35 2 06 0 96 76 9 3 57 1 95 1 02 87 2 4 3 00 2 02 0 65 34 6 2 63 2 30 0 57 26 6 2 91 2 13 0 63 32 6 3 16 2 01 0 68 38 4 3 39 1 88 0 73 44 1 5 2 84...

Page 15: ...11 60 7 3 40 2 88 0 97 47 0 3 75 2 67 1 08 57 3 4 07 2 50 1 17 67 5 4 34 2 37 1 24 76 6 4 3 64 2 45 0 78 30 4 3 20 2 79 0 69 23 4 3 53 2 59 0 76 28 6 3 84 2 43 0 83 33 7 4 11 2 29 0 88 38 7 5 3 45 2...

Page 16: ...35 52 6 4 15 3 51 1 19 40 7 4 58 3 26 1 31 49 6 4 98 3 06 1 43 58 5 5 30 2 90 1 52 66 3 4 4 45 3 00 0 96 26 3 3 91 3 41 0 84 20 3 4 32 3 16 0 93 24 8 4 69 2 97 1 01 29 2 5 02 2 79 1 08 33 5 5 4 21 2 8...

Page 17: ...30 0 4 83 4 09 1 38 23 2 5 33 3 79 1 53 28 3 5 79 3 56 1 66 33 3 6 16 3 37 1 77 37 8 4 5 18 3 48 1 11 15 0 4 54 3 96 0 98 11 6 5 02 3 68 1 08 14 1 5 45 3 46 1 17 16 7 5 84 3 25 1 26 19 1 5 4 9 3 34 0...

Page 18: ...82 55 2 5 58 4 72 1 60 42 7 6 16 4 38 1 77 52 1 6 69 4 11 1 92 61 4 7 12 3 90 2 04 31 5 4 5 98 4 03 1 29 27 6 5 25 4 58 1 13 21 3 5 80 4 25 1 25 26 0 6 30 4 00 1 36 30 7 6 76 3 75 1 45 15 9 5 5 66 3 8...

Page 19: ...4 52 1 75 40 8 5 6 82 4 64 1 17 18 3 5 85 5 39 1 01 13 5 6 60 4 95 1 14 17 2 7 19 4 61 1 24 20 4 7 74 4 32 1 33 23 6 6 6 37 4 47 0 91 11 1 5 40 5 22 0 77 8 0 6 14 4 79 0 88 10 3 6 80 4 40 0 97 12 6 7...

Page 20: ...0 65 70 TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD 10 1 20 0 10 0 7 1 88 0 16 1 8 2 60 0 22 3 4 3 28 0 28 5 4 3 96 0 34 7 8 4 66 0 40 10 8 5 33 0 46 14 2 6 00 0 52...

Page 21: ...TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD 10 3 18 0 27 0 6 4 99 0 43 1 4 6 91 0 59 2 6 8 72 0 75 4 1 10 54 0 91 6 1 12 39 1 07 8 4 14 18 1 22 11 0 15 97 1 37 13...

Page 22: ...e packaging material in accordance with current legislation at the appropriate waste reception or recycling site The units may be moved or lifted either by hand or by means of a suitable trolley If th...

Page 23: ...technicians trained to work with air conditioning and refrigeration systems Incorrect installation could lead to unit malfunctioning and a consequent deterioration in performance For installation foll...

Page 24: ...ch are marked Flow and Return All the water coils including the optional extras are equipped with air release valves next to the upper union and with water drain valves next to the lower union All the...

Page 25: ...on the left It is possible to turn the coil round to achieve connection on the right The operation of turning the principal and supplementary coils round can be carried out on site but it is preferab...

Page 26: ...ngle phase at 50Hz that the available power is sufficient for the running the equipment and that the supply cables are of adequate section for the maximum current which will be required Make sure that...

Page 27: ...o not use pointed objects through the air intake grilles Disconnect the power supply before cleaning and maintenance Use dry cloth to clean the unit Always disconnect the unit from the mains power sup...

Page 28: ...it Tighten the electrical contacts and terminals Check the unit s power using a clip on ammeter and compare with the values shown on the document Replace the fan assembly In case of burnout of the fan...

Reviews: