Ceiling/Wall Surface & Recess Mount Exit Signs 

 

          

OPERATING INSTRUCTIONS   1

 

CMEXR, MMEX, METDU, METSR, METSU, and METSW Series 

IMPORTANT SAFEGUARDS 

When using electrical equipment, basic safety precautions should always be followed, including the following:

 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON 

FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. FOLLOW 

ANY SPECIFIC INSTRUCTION ON LUMINAIRE LABELS.

 

 Do not mount near gas or electric heaters. 

 Equipment should be mounted in locations and at heights where it will not be readily subject to tampering by unauthorized personnel. 

 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 

 Do not use this equipment for other than intended use. 

 Servicing of this equipment should be performed by qualified personnel. 

 WARNING: Disconnect power to the circuit before wiring fixture. 

 Read all fixture markings and labels to insure correct installation of the fixture. Additional information may be located on the fixture or 

in supplemental instructions sheets, separate from this instruction sheet, regarding orientation, mounting restrictions and optional 

equipment. 

                                                          SAVE THESE INSTRUCTIONS

 

OPERATING INSTRUCTIONS

 

APPLICATIONS 

Mighty Mac MMEX series, Millenium Metrex METDU, METSR, METSU, METSW series, SimpleSeal CMEXR series exit signs 

with EL or CEL Emergency Battery Pack options. See fixture labels for instructions. METSW unit shown, other units similar.

 

 

FEATURES

 

-

 

Sealed, maintenance-free nickel-cadmium battery. EL option is suitable for use in 10 C (50 F) to 45 C (113 F) environments. 

CEL option includes a thermostatically controlled battery warmer and is suitable for use in -45 C (-49 F) to 45 C (113 F) 

environments. Self-testing circuitry automatically conditions the battery and performs regularly scheduled tests that conform 

to NFPA 101 Life 

-

 

Safety Code. Self-diagnostic circuitry monitors battery, charger, power transfer and lamp functions. 

 

INSTALLATION 

-

 

Follow Kenall Installation Instruction Sheet for proper mounting, 

assembly and wiring of unit. 

-

 

Fixture is shipped with battery disconnected. 

-

 

After installing electrical chassis and making field wiring connections (AC 

power OFF), connect polarized 2-pin battery connector to PC board 

assembly. 

-

 

Exit legend will illuminate for a few seconds and then extinguish. This 

signals that the battery is properly connected and is protected from 

discharging until AC power is established. 

-

 

Carefully align front stencil assembly over status/test pushbutton and 

indicator. Snap front stencil assembly to housing. 

 

START-UP 

-

 

Do not apply power to fixture unless supply can be maintained for at least 7 days without interruption. 

-

 

If battery is not connected when power is applied, the self-diagnostic feature will detect the missing battery and the status 

LED will display a steady red signal. Connect the battery and reset the system by pressing and holding the manual push test 

switch for approximately 7 seconds. 

-

 

Upon initial power-up, the fixture will supply a trickle charge to the battery for 90 minutes. Then it will switch to full charge 

mode for approximately 24 hours. The fixture will then condition the battery with a pair of 90 minute discharge and 24 hour 

recharge cycles. 

LOAD LEARNING 

-

 

During the final discharge/recharge cycle of the battery conditioning function, the self-diagnostic feature will measure the 

operating current of the internal and external (if equipped) exit sign(s). 

-

 

Any time the total (internal or external) exit sign load is intentionally altered, the system must be reset by pressing and 

holding the manual test pushbutton for approximately 7 seconds. Failure to do so will result in a lamp fault indication. 

 

NORMAL OPERATION 

Normal operation is indicated by a steady green signal from the status LED. This indicates the fully charged battery is receiving 

a maintenance (trickle) charge and normal AC power is present. The normally on exit sign(s) will operate from normal AC power

 

 

           