Marker arrow
Balancing head
Rotary shutt-off cap
Locking screw M5
Adjusting cap
Hex key size 2,5 mm
Plug
3
Accessories
3.1
Dial Thermometer
ð
Figure T5100 150 00
3.2
Remove rotary shut-off cap and insert ther-
mometer into the provided hole as far as it
will go.
To relay the temperature to a building ser-
vices control system, a Pt 1000 temperature
sensor, instead of the thermometer, can be
inserted in the hole.
(For 1/2” hose with 3/4” union nut) Unscrew
plug from drainage connection. Screw drain
valve into place and tighten.
Turn adjustable ring on drain valve to „Zu“
(Closed) position (clockwise). For drainage,
connect hose and turn to „Auf“ (Open) po-
sition.
Filling and drain valve:
ð
Figure J7109 173 00
3.3
Insulating shell:
ð
Figure 471 11
3.4
Material: PE material, fire safety class B1 to
DIN 4102, Part 1.
The one-piece, closable insulating shell can be
fastened by means of the clips included in the
scope of supply or cemented in place using
commercially available adhesive.
§
Pt 1000, T = 0 - 100 °C
§
4-conductor
§
tolerance class A
§
connection 2 m, 4 x 0,35 mm²
§
pre-assembled
Temperature sensor Pt 1000:
ð
Figure T5100 140 00