2.3.1
CAN bus cable
Bus cables for the wiring of CAN bus systems (controller area network) in accordance with
ISO 11898 must be used for bus systems with 120 Ω nominal impedance. Only when such
cables are used can a high level of data transfer security be guaranteed.
Recommended properties for the CAN bus cable
Cable type
CAN bus cable
Conductor material
Kupfer
Conductor cross-section and number of
wires
Cross-section Length
1 x 2 x 0,34 mm²
1 x 2 x 0,50 mm²
1 x 2 x 0,75 mm²
300 m
500 m
1000 m
Shielding
Braiding of tinned copper wires
Impedance at f
≥
1Hz
120 Ω
±
15 %
2.3.2
CAN-Bus-Anschluss
Components
Designation
Number
of subscribers
per component
Max. number of
components per
-MASTER-
Control System SLAVE
1
62
KHS HS2 Hygiene
flushing box with one
connection
+
Can bus connection set
1
60
KHS HS2 Hygiene
flushing box with two
connections
+
Can bus connection set
2
30
The KHS Mini Control System has two
integrated CAN bus connections with
which up to 62 CAN bus participants can
be addressed. A maximum of 31 bus
subscribers can be connected to each
CAN bus connection.
max. 31 CAN
bus subscribers
max. 1000 m
(in total)
max. 31 CAN bus
subscribers
max. 1000m (in
total)
CAN bus
Connection B
CAN bus
Connection A
2
1