K410062000000-00 / 05.2017
7
3
Technical data | Dimensions
3.1
Leak controller
3.2
Water sensor
4
Assembly | Electrical connection
Caution!
Only allow certified specialized plumbers to install and mount electrical equipment.
Very strong magnetic fields can impair the functioning. Interference can be prevented by complying
with the installation rules below:
Do not mount the controller and water sensors near inductive loads (motors, transformers,
contactors, etc.).
Feed through a separate mains voltage circuit (if necessary, with mains filter).
Inductive loads must be equipped with protective devices to reduce overloads (varistors, RC
filter).
When using the controller together with other devices in one system, check to see whether that
causes interference signals to be emitted. For long cable connections of > 50 m for the water sensor,
follow the instructions for wiring in 3.1 to prevent interference.
Connection lead: 2 x 0,4 mm²