Roof flashing supplied
by contractor
Stainless steel
double cone
cow l
1000mm minimum distance
above roof line or 600 minimum
above ridge if penetration
closer than 3 meters to ridge
Stainless steel flue pipe.
All flue pipes must be
connected w ith pop rivets
supplied by installer
25mm min
clearance
12mm min air gap
betw een ceiling line
and celling plate
Vented cap
Decroshield
150mm min
NOTE:
When decromesh/heatsheild is fitted, it must finish a minimum 600mm below
the ceiling or extend through the ceiling drop box into the outer flue casing.
Alw ays cover flue completely until installation and cleanup is complete.
Support outer flue w ith
bracket supplied. Run a
bead of silicon dow n seam
of outer casing to ensure
against leaks.
Pop rivet or
screw brackets to
the outside of the
outer casing
Short tube fits into flue
pipe. All flues should
be trimmed level
INSTALLATION INSTRUCTION
TRIPLE FLUE KIT
INSTALLATION TO COMPLY WITH AS/NZS 2918
A
DETAIL A
DETAIL B
RAKED CEILING
Decroshield
6” Flue
8” Flue
10” Flue
10” Flue
8” Flue