8  Installation instructions  

Kelvinator Air Conditioning

Outer diameter (mm)

A(mm)

Max.

Min.

φ

6.35

1.3

0.7

φ

9.53

1.6

1.0

φ

12.7

1.8

1.0

φ

16.0

2.4

2.2

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A

"

Tightening connection

•  Align the centre  of the pipes.
•   Sufficiently tighten the flare nut with fingers, and 

then tighten it with a spanner and torque wrench 
as shown below.

Indoor unit tubing

Flare nut

Piping

s

Outer 

diameter

Tightening torque 

(Kg.m)

Additional tightening 

torque (Kg.m)

φ

6.35

1.6

2.0

φ

9.53

3.0

3.5

φ

12.7

5.0

5.5

φ

16.0

7.5

8.0

caution

•   Excessive torque can break nut depending on 

installation conditions.

E:  Check

•  Compare the flared work with the adjacent diagram.
•   If flare is found to be defective, cut off the flared section 

and do flaring work again.

Smooth all round

 Improper flaring

Even length

all round

Flaring work

Main cause for refrigerant leakage is due to defects in 
the flaring work. Carry out correct flaring work using the 
following procedure:

Oblique

90 C

Roughness

Burr

A:  Cut the pipes and the cable

•   Use the piping kit accessory (if applicable) or pipes 

purchased locally.

•   Measure the distance between the indoor and the 

outdoor unit.

•  Cut the pipes a little longer than the measured distance.
•  Cut the cable 1.5m longer than the pipe length.

B:  Burr removal

•   Completely remove all burrs from the cut cross section 

of pipe/tube.

•   Face the end of the copper pipe/tube in a downward 

direction as you remove burrs in order to avoid burrs 
dropping into the tubing.

Pipe

Reamer

Face down

caution

C:  Putting flare nut on

•  Remove flare nuts attached to indoor and outdoor unit, 
 

then put them on pipe/tube having completed burr  

 removal.

Note: It is not possible to put them on after flaring work.

Flare nut

Copper tube

D:  Flaring work

•  Carry out flaring work using flaring tool as shown below.
•   Firmly hold copper pipe in a die according to the 

dimension shown in the following table.

Refrigerant pipe connection

Summary of Contents for KSV80HRC

Page 1: ...Inverter Split Room Air Conditioner Installation Manual KSV26CRC KSV26HRC KSV35CRC KSV35HRC KSV53HRC KSV62HRC KSV70CRC KSV70HRC KSV80HRC Refrigerant R410A...

Page 2: ...to discard this air conditioner please contact your local authorities and ask for the correct method of disposal caution The air conditioner is not intended for use by young children or infirmed perso...

Page 3: ...uits must be disconnected Please read this installation manual and the user manual before installation and store in a handy place for later reference Inside you will find many helpful hints on how to...

Page 4: ...tic waves are generated by radio equipment welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains...

Page 5: ...sions are not adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access space nec...

Page 6: ...tside the outlet pipe The drain hose should be slanted downward slightly without distortion bulge or fluctuation Do not put the outlet into water Installation of indoor unit Installation of the mounti...

Page 7: ...om the left or right side of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and taili...

Page 8: ...nt leakage is due to defects in the flaring work Carry out correct flaring work using the following procedure Oblique 90 C Roughness Burr A Cut the pipes and the cable Use the piping kit accessory if...

Page 9: ...connection green Air purging and leakage test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of chargi...

Page 10: ...city is not accurate Operation test 1 Before operation test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off val...

Page 11: ...less the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii mis...

Page 12: ...bout Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www ke...

Reviews: