Kelvinator KSV26HRB Installation Manual Download Page 7

Kelvinator Air Conditioning 

 refrigerant pipe connection  13

12  refrigerant pipe connection  

Kelvinator Air Conditioning

For rear left piping

Note: When viewed from the front of the indoor unit.

A:   Route the indoor tubing and the drain hose to the 

required piping hole position in the direction of left.

Tubing retainer

B:   Insert the connecting cable into the indoor unit from 

the outdoor unit through the piping hole.

•    Do not connect the cable to the indoor unit.
•    Make a small loop with the cable for easy 

connection later.

C:   Tape the drain hose and the connecting cable. Be sure 

that the drain hose is located at the lowest side of the 
bundle. locating at the upper side can cause drain pan 
to overflow inside the unit.

Note:  If the drain hose is routed inside the room, insulate 

the hose with an insulation material so that dripping 
from “sweating” (condensation) will not damage 
furniture or floors. 
*Foamed polyethylene or equivalent is recommended.

G:   Connecting the piping to the indoor unit and the drain 

hose to drain pipe.

•   Align the centre of the piping and sufficiently tighten the 

flare nut by hand.

•    Tighten the flare nut with a wrench, in accordance with 

the following table.

Outer 

Diameter.

Tightening torque 

(Kg.m)

Additional Tightening 

Torque (Kg.m)

1/4” (6.35mm)

1.6

2.0

3/8” (9.53mm)

3.0

3.5

1/2” (12.7mm)

5.0

5.5

5/8” (16.0mm)

7.5

8.0

Indoor unit tubing

Flare nut

Piping

s

•     When extending the drain hose of the indoor unit, 

install the drain pipe extension as shown in 
diagram below.

H:   Wrap in the insulation material around the 

connecting portion.

•     Overlap the connection pipe heat insulation and the 

indoor unit pipe heat insulation material. Bind them 
together with vinyl tape so that there is no gap.

•     Wrap the area which accommodates the rear piping 

housing section with vinyl tape.

•     Bundle the piping and drain hose together by wrapping 

them vinyl tape over the range within they fit into the rear 
piping housing section.

C:   Tape the tubing, drain hose and the connecting cable. 

Be sure that the drain hose is located at the lowest side 
of the bundle. Locating at the upper side can cause 
drain pan to overflow inside the unit.

Note: If the drain hose is routed inside the room, insulate the 
hose with insulation material so that dripping from “sweating” 
(condensation) will not damage furniture or floors. 
*Foamed polyethylene or equivalent is recommended.

D:   Insert the piping, drain hose and the connecting cable 

into the piping hole.

Tubing retainer

E:   Set the piping and the drain hose to the back of the 

chassis with the tubing holder.

•    Set the tubing retainer into position and tighten screw.

Connecting

cable

F:   Locating the indoor unit

•     Hook the indoor unit onto the upper portion of 

the installation plate (Engage the two hooks of the 
installation plate into the openings at the rear top of 
the indoor unit). Ensure that the hooks are properly 
seated on the installation plate by moving the indoor 
unit left and right.

•    Press the lower left and right sides of the unit against the 

installation plate unit until the hooks engage into their 
slot (clicking sound).

Connection of pipes - Indoor

•   Prepare the indoor unit’s piping and drain hose for 

installation through the wall.

•   Remove the tubing retainer (see illustration below) 

and pull the tubing and drain hose away from chassis 
(if required). For some models this is not needed.

•   Replace the tubing retainer in its original position.

Tubing retainer

caution

When installing the indoor unit, be sure to remove the 
relavant sections where required (see adjacent diagram 
for example). This will allow piping and cable routing to 
be completed without damaging the unit.

For rear right piping

Note: When viewed from the front of the indoor unit.

A:   Route in indoor tubing and the drain hose in the 

direction of rear right.

B:   Insert the connecting cable into the indoor unit from 

the outdoor unit through the piping hole.

 

• Do not connect the cable to the indoor unit.

 

•  Make a small loop with the cable for easy 

connection later.

Rear left

Drain hose

Piping

Connecting cable

Rear right

Front

Summary of Contents for KSV26HRB

Page 1: ...Inverter Split type Room Air Conditioner Installation Manual KSV26HRB KSV35HRB KSV53HRB KSV62HRB KSV70HRB KSV80HRB Refrigerant R410A ...

Page 2: ...g the appliance tips and information This symbol indicates tips and information about use of the appliance environmental tip This symbol indicates tips and information about economical and ecological use of the appliance This symbol indicates never to do this This symbol indicates always do this Important safety instructions 2 Contents Kelvinator Air Conditioning Congratulations and thank you for ...

Page 3: ...fied torque wrenches 1 8kgf m 4 2kgf m 5 5kgf m 6 6kgf m different depending on model No Spanner half union Hexagonal wrench 4mm Gas leak detector Vacuum pump Gauge manifold Users manual Thermometer Multimeter Pipe cutter Measuring tape Items required for installing the unit Number Name of Accessories Qty 1 Installation Plate 1 2 Clip Anchor 8 3 Self tapping Screw A 8 4 Seal See page 8 for details...

Page 4: ... unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the space on the left and right of the unit is more than 12cm Use a stud finder to locate studs to prevent unnecessary damage to the wall The indoor unit should be installed on the wall at a height of 2 0m or more from the floor The indoor unit should be installed allowing a minimum...

Page 5: ... pipe hole 65 Left rear side refrigerant pipe hole 65 12cm or more to wall 12cm or more to wall 850 45 90 45 45 272 80 489 6 2kw model 12cm or more to the wall to the wall 12cm or more 50 15cm or more to the ceiling Indoor Unit Outline 380 Hooked Part 380 998 322 119 130 65 65 130 50 Above 12cm to the wall Above 12cm to the wall Above 15cm to the ceiling 325 55 95 95 55 1250 815 257 178 55 58 Pipe...

Page 6: ...ing of outdoor unit Anchor the outdoor unit with a bolt and nut 10 or 8 tightly and horizontally on a concrete or rigid mount Model A mm B mm 3 5kw 530 290 5 3kw 560 335 6 2kw 590 333 A B Air inlet Air outlet Air inlet Drain joint installation If a drain elbow is used the unit should be placed on a stand which is taller than 3cm If the unit is used in an area where temperature falls below 0O C for...

Page 7: ...ing section C Tape the tubing drain hose and the connecting cable Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Note If the drain hose is routed inside the room insulate the hose with insulation material so that dripping from sweating condensation will not damage furniture or floors Foamed polyethy...

Page 8: ...n screw Tubing retainer I Reroute the piping and the drain hose across the back of the chassis for rear left side external passage J Locating the indoor unit Remove the spacer Hook the indoor unit onto the upper portion of the installation plate Engage the hooks of the installation plate into the openings at the rear top of the indoor unit Ensure that the hooks are properly seated on the installat...

Page 9: ...rcuit diagram posted on the inside of the control cover 2 The screws which fasten the wiring in the casing of electrical fittings may come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could cause burn out of the wires 3 Specification of power source 4 Confirm that electrical...

Page 10: ...an the atmosphere pressure 7 Remove the charge hose from the Low pressure charge hose 8 Fully open the packed valve stems B and A 9 Securely tighten the cap of the packed valve Manifold valve Compound meter 76cmHg Handle L o Handle Hi Charge hose Charge hose Vacuum pump Pressure gauge Low pressure valve Air purging Air purging Air and moisture in the refrigerant system have undesirable effects as ...

Page 11: ...AUTO or COOL mode see User Manual for details The test operation should last about 30 minutes Manual control button AUTO COOL Rated Capacity Test Cooling mode Under Cooling Mode set the air conditioner at High Fan Speed and set the temperature to 17O C then press the TURBO button 6 times within 10 seconds be sure the indoor unit buzzes 6 times The system will enter Rated Capacity Test mode The buz...

Page 12: ...rchase is required before you can make a claim under this warranty 7 You may not make a claim under this warranty unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and t...

Page 13: ...rmation about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...