Kelvinator KSV26CRE Installation Manual Download Page 7

Kelvinator Air Conditioning

  Installation instructions  7

15    Note low temperature soldering alloys are not acceptable.
16   Minimum room space requirements as advised on the 

rating plate must be complied with.

17    Reusable mechanical connectors may not be used within 

indoors or within wall or ceiling cavities where a refrigerant 
leak can gather.

18   All refrigerant tubing shall be protected or enclosed to 

prevent damage.

Outdoor unit

1   Select a site where noise and outflow air emitted by unit will 

not annoy neighbours.

2   Select a site where there is sufficient ventilation.
3   Select a site where there is no obstruction blocking the inlet 

and outlet.

4   The site should be able to withstand the full weight and 

vibration of the unit.

5   Select a dry place, but do not expose the unit to direct 

sunlight or strong wind.

6   Make sure that the outdoor unit is installed in accordance 

with the installation instructions, and is convenient for 
maintenance and repair.

7   Select a place where it is out of reach of children and far 

from animals or plants.

8   Select a place where the unit keeps the horizontal and 

aligned position.

9   Select at a place that respects the minimum distances 

around the outdoor unit as below:

more than 20cm

more than 

50cm

more than 

30cm

more than 1.5m

10   Note low temperature soldering alloys are not acceptable.
11    Reusable mechanical connectors may not be used within 

indoors or within wall or ceiling cavities where a refrigerant 
leak can gather.

Installation site instructions

A proper installation site is vital for correct and efficient 
operation of the unit.

Avoid the following sites where:
•   strong heat sources, vapour, flammable gas or volatile 

liquids are emitted.

•   high-frequency electro-magnetic waves are generated by 

radio equipment, welders or medical equipment.

•   salt-laden air prevails (such as close to coastal areas).
•   the air is contaminated with industrial vapours and oils.
•   the air contains sulphurous gas such as in hot  

spring zones.

•   corrosion or poor air quality exists.

Indoor unit

1  The air inlet and outlet should be kept clear of obstructions. 

Ensure the air can be blown through the whole room.

2  Select a site where the condensing water can be easily 

drained out, and where it is easily connected to the  
outdoor unit.

3  Select a place where it is out of reach of children.
4  Select the place where the wall is strong enough to 

withstand the full weight and vibration of the unit.

5  Be sure to leave enough space to allow access for routine 

maintenance.

6  For optimum performance, the indoor unit should be 

installed on the wall at a height of 2 metres or more above 
the floor and at least 2.5 metres from the opposing wall.

7  Make sure that the indoor unit is installed in accordance with 

installation dimension as below:

more than 15cm from 

the ceiling

more than 

15cm

more than 

15cm

more than 2m from the floor

more than 2.5m from the 

opposing wall

8   Select place about 1m or more away from a TV set or any 

other electric appliance.

9   Select a place where the filter can be easily taken out.
10   Do not use the unit in the laundry or by swimming pool etc.
11   A minimum pipe run of 3 metres is required to minimise 

vibration and noise.

12   Use a stud finder to locate studs to prevent unnecessary 

damage to the wall.

13   Any variations in pipe length may require adjustment to 

refrigerant charge.

14   Do not install near a doorway.

Summary of Contents for KSV26CRE

Page 1: ...Inverter Room Air Conditioner Installation Manual KSV26CRE KSV26HRE KSV35CRE KSV35HRE KSV53HRE KSV62HRE KSV70CRE KSV70HRE KSV80HRE Refrigerant R32 ...

Page 2: ... but contact your local Electrolux Customer Care Centre Meanings of symbols used in this manual are shown below warning This symbol indicates information concerning your personal safety caution This symbol indicates information on how to avoid damaging the appliance tips and information This symbol indicates tips and information about use of the appliance environmental tip This symbol indicates ti...

Page 3: ...nual and the user manual before installation and carefully store in a handy place for later reference Inside you will find many helpful hints on how to install and test the air conditioner properly Electrical work must be installed by a licensed electrician Be sure to use the correct rating of the power plug and main circuit for the model to be installed Incorrect installation due to ignoring this...

Page 4: ...ge Screw driver Electric drill Hole core drill 55mm 70mm Flaring tool specifically designed for R32 or R410a refrigerant Specified torque wrenches Spanner half union A glass of water Hexagonal wrench 6mm Gas leak detector Vacuum pump Gauge manifold Users manual Thermometer Multimeter Pipe cutter Measuring tape Number Description Quantity 1 Indoor unit mounting plate 1 fan 2 Clip anchor not supplie...

Page 5: ...tdoor unit space to obstruction air inlet side space to the wall space to the wall space to the ceiling space to the floor air outlet side 15cm or more 200cm or more 15cm or more 2 5 0 c m o r m o re 15cm or more space to the wall air outlet side 30cm or more 50cm or more space to the wall 50cmormore 20cm orm ore 150cm orm ore 1 8 9 10 11 12 13 14 15 16 17 7 6 5 4 ...

Page 6: ...cessible without special equipment Has the appropriate size circuit and fuse circuit breaker been fitted Has the unit been tested and confirmed to operate correctly Has the user of the air conditioner been shown how to use the air conditioner CUSTOMER PLEASE RETAIN WITH YOUR PURCHASE DOCUMENTS IN A SAFE PLACE Model Number ____________________________________________________________________________...

Page 7: ...unit Avoid the following sites where strong heat sources vapour flammable gas or volatile liquids are emitted high frequency electro magnetic waves are generated by radio equipment welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zones corrosion or poor ...

Page 8: ...n reliability Exceeding the maximum may cause poor performance or malfunction When the level difference between indoor and outdoor units is greater than the maximum height of 10 metres or when the outdoor unit is installed above the indoor unit an oil trap should be installed every 5 7 metres Pipe Length Elevation and Additional Quantity of Gas Model Number Suction Pipe Diameter Discharge Pipe Dia...

Page 9: ...xing the 4 holes existent in its base with 4 bolts and nuts of φ10 mm tightly not included Place the outdoor unit over a horizontal concrete or rigid surface never directly over grass or earth A B air inlet air inlet air outlet Model Outdoor unit dimensions W x D x H mm Dimension A mm Dimension B mm KSV26HRE CRE 776 x 320 x 540 510 286 KSV35HRE CRE 842 x 320 x 596 540 286 KSV53HRE KSV62HRE KSV70CR...

Page 10: ... the indoor unit has two way drainage design During installation the indoor unit should slightly slant to water tray s outlet for smooth drainage of condensate water Fit the mounting plate and drill holes in the wall according to the wall structure and corresponding mounting points on the mounting plate dimensions are in mm unless otherwise stated Model no Indoor unit dimension W x D x H mm Mounti...

Page 11: ...Installation instructions 11 Mounting plate type C Mounting plate type D Indoor unit installation 70 70 36 67 67 36 146 90 65 575 left right indoor unit indoor unit 172 253 179 746 1073 183 685 149 326 337 65 65 50 163 90 6 74 105 ...

Page 12: ...hrough the hole 4 Always use a wall hole conduit when drilling metal grids metal plates or the like 5 For models with a cooling capacity greater than 4500W remove and dispose the two polystyrene lateral rear supports from the indoor unit before the installation remove both supports Installation of drain hose 1 Connect the drain hose to the outlet pipe of the indoor unit Bind the joint with vinyl t...

Page 13: ... routing the wiring only Cut off the tailings 1 and tailings 2 when routing both the wiring and piping indoor unit outline connection piping 43 2 The drain hose can be connected at two different positions Use the most convenient position and if necessary exchange the position of drain cap and drain hose The drain hose is connected at the rear left side of the indoor unit when you receive the produ...

Page 14: ... hose from the right side piping on the right side drain hose from the left side piping on the right side drain hose from the right side piping on the left rear side drain hose from the left side piping on the left side drain hose from the left side caution When refrigerant pipes and the drain pipe are fitted to the same side ensure that the bulk does not push the unit away from the wall when in i...

Page 15: ... the bundle Locating at the upper side can cause drain pan to overflow inside the unit Never cross connect or interwind the power wire with any other wiring Do not allow the piping to be exposed out from the back of the indoor unit If part of the drain hose is positioned inside the room wrap it with insulating materials so as to prevent condensed water from dropping 5 Hang the mounting slots of th...

Page 16: ... cross section of pipe tube Face the end of the copper pipe tube in a downward direction as you remove burrs in order to avoid burrs dropping into the tubing pipe reamer face down c Put the flare nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal flare nut copper tube caution It is not possible to put them on after flaring work d F...

Page 17: ...rtion Cover the indoor unit pipe and the connection pipe with the heat insulation material Bind them together with vinyl tape so that there is no gap insulating material Isolate the suction pipe from the liquid pipe heat insulation suction line pipe liquid line pipe Wrap the insulated pipes with vinyl tape in the rear section for pipe housing Fasten the power cable to the pipes with vinyl tape con...

Page 18: ...ge pipe for KSV53HRE and KSV62HRE Make sure to follow the torque table value as below Outer diameter mm Torque N m 6 35 1 4 15 16 9 52 3 8 31 32 12 70 1 2 40 41 15 88 5 8 45 46 Piping formation a Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with narrow vinyl tape and wide vinyl tape If you want to connect an additional drain hose the ...

Page 19: ...ional wiring regulations 4 A circuit breaker with proper capacity must be installed according to AS3000 and applicable local electrical safety regulations 5 In case of problems in power supply the air conditioner must not be installed before the customer fixes the problem 6 Be sure the power supply matches the air conditioner 7 Ensure the live wire neutral wire and earth wire in the power socket a...

Page 20: ...es that are not connected with insulating tape so that they do not touch any electrical or metal parts 5 Secure the wires firmly with the cable clamp 6 Put the wiring cover back and screw it 7 Reinstall the front panel warning All wires between indoor and outdoor units must be connected by a qualified electric contractor If the length of the power cord is not enough please contact your installer f...

Page 21: ...ng the above conditions prepare the wiring as follows The screws which fasten the wiring to the terminal block may come loose from vibrations during transportation Check and make sure all screws are well fixed Otherwise it could cause burn out of the wires Be sure the circuit capacity is sufficient Ensure the starting voltage is maintained at over 90 of the rated voltage marked on the nameplate Co...

Page 22: ...igeration circuit may freeze and block the capillary tubing Water may lead to corrosion of parts in the refrigeration system Therefore the indoor unit and tubing between the indoor and outdoor units must be tested for leakage and evacuated to remove any non condensables and moisture from the system Air purging with a vacuum pump Preparation Check that each tube both liquid and gas side tubes betwe...

Page 23: ... the flare nut of the low pressure valve to check if there is air coming inside if operation noise of the vacuum pump has been changed the reading of multimeter is 0 instead of minus Then tighten the flare nut 5 Keep vacuuming for more than 15 minutes and make sure the reading of multimeter is 1 0 x 10 Pa 76cmHg Then fully close the low handle of manifold valve and stop the operation of the vacuum...

Page 24: ...st Do not switch on power before installation is finished completely Electric wiring must be connected correctly and securely Stop valves of the connection pipes should be fully opened All the impurities such as scraps and waste must be cleared from the unit Operation test method Switch on power and press ON OFF button on the remote controller to start the operation Press MODE button to select the...

Page 25: ...ge Is the voltage in accordance with the rated voltage marked on the nameplate It may cause electric malfunction or damage the unit Is the electric wiring or piping connection installed correctly and securely It may cause electric malfunction or damage the parts Has the unit been securely earthed It may cause electrical leakage Is the power cord specified It may cause electric malfunction or damag...

Page 26: ...26 Notes Kelvinator Air Conditioning Notes ...

Page 27: ...nless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi inco...

Page 28: ...about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...

Reviews: