Installation instructions

1  Flaring work

Main cause for refrigerant leakage is due to defects in the flaring 
work. Carry out correct flaring work using the following procedure:

Oblique

90 C

Roughness

Burr

A:  Cut the pipes and the cable.

1.   Use the piping kit accessory (if applicable) or pipes purchased locally.

2.   Measure the distance between the indoor and the outdoor unit.

3.  Cut the pipes a little longer than the measured distance.

4.  Cut the cable 1.5m longer than the pipe length.

B:  Burr removal

 

1. 

 Completely remove all burrs from the cut cross section 
of pipe/tube.

 

2. 

 Face the end of the copper pipe/tube in a downward 
direction as you remove burrs in order to avoid burrs 
dropping into the tubing.

Pipe

Reamer

Face down

WARNING

caution

C:  Putting flare nut on

Remove flare nuts attached to indoor and outdoor unit, 
then put them on pipe/tube having completed burr removal

Note: It is not possible to put them on after flaring work.

Flare nut

Copper tube

D:  Flaring work

• 

Carry out flaring work using flaring tool as shown below.

• 

 Firmly hold copper pipe in a die according to the dimension 
shown in the table below.

Refrigerant pipe connection

Outer diam. (mm)

A(mm)

Max.

Min.

φ

6.35

1.3

0.7

φ

9.53

1.6

1.0

φ

12.7

1.8

1.0

φ

16.0

2.4

2.2

 

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A

"

 

Flaring tool assembly torque

Outer diam.

Tightening torque 
(N.m)

Additional Tightening 
Torque (N.m)

φ6.35

1.6

2.0

φ9.53

3.0

3.5

φ12.7

5.0

5.5

φ16.0

7.5

8.0

WARNING

caution

• 

 Excessive torque can break nut depending on installation 

conditions.

E: Check

• 

Compare the flared work with the adjacent diagram.

• 

 If flare is found to be defective, cut off the flared section and 
do flaring work again.

Smooth all round

 Improper flaring

Even length

all round

Summary of Contents for KSV25HRD

Page 1: ...Inverter Split Room Air Conditioner Installation Manual KSV25HRD KSV35HRD KSV52HRD KSV70HRD KSV80HRD Refrigerant R410A ...

Page 2: ...your local Electrolux Customer Care Centre ENVIRONMENTAL TIPS environment Information on disposal for users Most of the packing materials are recyclable Please dispose of those materials through your local recycling depot or by placing them in appropriate collection containers If you wish to discard this air conditioner please contact your local authorities and ask for the correct method of dispos...

Page 3: ...responsible for their safety 7 Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnected Please read this installation manual and the user manual before installation and carefully store in a handy place for later reference Inside you will find many helpful hints on how to install an...

Page 4: ...ent welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zones corrosive or poor air quality exists Installation Site of Indoor Unit 1 The air inlet and outlet should be away from the obstructions Ensure the air can be blown through the whole room 2 Select a...

Page 5: ... adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access by a service technician space necessary for proper installation of the unit with respect to existing building structure Space to the wall 150cm horizontally in front Space to the obstruction Air outlet side e v o b 50cm A ...

Page 6: ...he outlet in the water Installation of indoor unit Installation of Mounting Plate 1 The mounting plate should be installed horizontally As the water tray s outlet for the indoor unit is two way type during installation the indoor unit should slightly slant to water tray s outlet for smooth drainage of condenser water 2 Fix the mounting plate on the wall with screws 3 Be sure that the mounting plat...

Page 7: ... of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and tailings 2 when routing both the wiring and piping 2 Take out the piping from body case wrap the piping power cords drain hose with the tape and then make them pass through the piping hole As shown in Fig 2 3 Hang the mounting slo...

Page 8: ...move flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal Note It is not possible to put them on after flaring work Flare nut Copper tube D Flaring work Carry out flaring work using flaring tool as shown below Firmly hold copper pipe in a die according to the dimension shown in the table below Refrigerant pipe connection Outer diam mm A mm Max Min...

Page 9: ...kage Test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of charging hose to vacuum pump 3 Fully open the handle of Lo manifold valve 4 Open the vacuum pump for vacuumisation At the beginning slightly loosen joint nut of low pressure valve to check if there is air coming inside If noise of vacuum pump...

Page 10: ...t accurate Operation Test 1 Before Operation Test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off valves of the connection pipes should be opened d All the impurities such as scraps and waste must be cleared from the unit 2 Operation Test Method a Switch on power and press ON OFF button on the remote controlle...

Page 11: ...hown in the fig For 5 2kW is as below Clasp of RJ45 plug of network cable shall aim at the notch of RJ45 terminal to be installed The clasp shall be towards inside as shown in the fig For 7 0kW and 8 0kW is as below Clasp of RJ45 plug of network cable shall aim at the notch of RJ45 terminal to be installed The clasp shall be towards left as shown in the fig Bundle the Dred network cable at the wir...

Page 12: ...12 Notes Notes ...

Page 13: ...13 Notes Notes ...

Page 14: ...14 Notes Notes ...

Page 15: ...ct claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi incorrect improper...

Page 16: ...nator com au NEW ZEALAND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call into your retailer phone or email our customer care team or visit our website Kelvinator We are part of the Electrolux family Share more of our thinking at electrolux com au ...

Reviews: