Kelvinator KSV25CRG Installation Manual Download Page 20

20  Information servicing 

Kelvinator Air Conditioning

Information servicing

Charging procedures 

In addition to conventional charging procedures, the following 
requirements shall be followed: 

• 

 Ensure that contamination of different refrigerants does not 
occur when using charging equipment. Hoses or lines shall 
be as short as possible to minimize the amount of refrigerant 
contained in them. 

• 

 Cylinders shall be kept upright. 

• 

 Ensure that the refrigeration system is earthed prior to 
charging the system with refrigerant. 

• 

 Label the system when charging is complete (if not already). 

• 

 Extreme care shall be taken not to overfill the refrigeration 
system. 

• 

 Prior to recharging the system it shall be pressure tested 
with OFN. The system shall be leak tested on completion of 
charging but prior to commissioning. A follow up leak test shall 
be carried out prior to leaving the site.

Decommissioning

Before carrying out this procedure, it is essential that the technician 
is completely familiar with the equipment and all its detail. It is 
recommended good practice that all refrigerants are recovered 
safely. Prior to the task being carried out, an oil and refrigerant 
sample shall be taken.

In case analysis is required prior to re-use of reclaimed refrigerant. 
It is essential that electrical power is available before the task is 
commenced. 

a)  Become familiar with the equipment and its operation. 

b)  Isolate system electrically. 

c)  Before attempting the procedure ensure that: 

 

• 

 Mechanical handling equipment is available, if required, 
for handling refrigerant cylinders; 

 

• 

 All personal protective equipment is available and being 
used correctly; the recovery process is supervised at 

 

• 

 All times by a competent person; 

 

• 

 Recovery equipment and cylinders conform to the 
appropriate standards. 

d)   Pump down refrigerant system, if possible. 

e)   If a vacuum is not possible, make a manifold so that refrigerant 

can be removed from various parts of the system. 

f) 

 Make sure that cylinder is situated on the scales before 
recovery takes place. 

g)   Start the recovery machine and operate in accordance with 

manufacturer's instructions. 

h)   Do not overfill cylinders. (No more than 80 % volume liquid 

charge). 

i) 

 Do not exceed the maximum working pressure of the cylinder, 
even temporarily. 

j) 

 When the cylinders have been filled correctly and the process 
completed, make sure that the cylinders and the equipment 
are removed from site promptly and all isolation valves on the 
equipment are closed off. 

k)   Recovered refrigerant shall not be charged into another 

refrigeration system unless it has been cleaned and checked. 

Labelling

Equipment shall be labelled stating that it has been  
de-commissioned and emptied of refrigerant. The label shall be 
dated and signed. Ensure that there are labels on the equipment 
stating the equipment contains flammable refrigerant.

Recovery

• 

 When removing refrigerant from a system, either for servicing 
or decommissioning, it is recommended good practice that all 
refrigerants are removed safely.

• 

 When transferring refrigerant into cylinders, ensure that only 
appropriate refrigerant recovery cylinders are employed. 
Ensure that the correct numbers of cylinders for holding the 
total system charge are available. All cylinders to be used are 
designated for the recovered refrigerant and labelled for that 
refrigerant (i.e. special cylinders for the recovery of refrigerant). 
Cylinders shall be complete with pressure relief valve and 
associated shut-off valves in good working order.

• 

 Empty recovery cylinders are evacuated and, if possible, 
cooled before recovery occurs.

• 

 The recovery equipment shall be in good working order with 
a set of instructions concerning the equipment that is at hand 
and shall be suitable for the recovery inflammable refrigerants. 
In addition, a set of calibrated weighing scales shall be 
available and in good working order.

• 

 Hoses shall be complete with leak-free disconnect couplings 
and in good condition. Before using the recovery machine, 
check that it is in satisfactory working order, has been properly 
maintained and that any associated electrical components are 
sealed to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

• 

 The recovered refrigerant shall be returned to the refrigerant 
supplier in the correct recovery cylinder, and the relevant 
Waste Transfer Note arranged. Do not mix refrigerants in 
recovery units and especially not in cylinders. If compressors 
or compressor oils are to be removed, ensure that they have 
been evacuated to an acceptable level to make certain that 
flammable refrigerant does not remain within the lubricant. 
The evacuation process shall be carried out prior to returning 
the compressor to the suppliers. Only electric heating to the 
compressor body shall be employed to accelerate this process. 
When oil is drained from a system, it shall be carried out safely.

Transportation, marking and storage for units

1.   Transport of equipment containing flammable refrigerants 

compliance with the transport regulations.

2.   Marking of equipment using signs compliance with local 

regulations.

3.   Disposal of equipment using flammable refrigerants 

Compliance with national regulations.

4.   Storage of equipment/appliances The storage of equipment 

should be in accordance with the manufacturers instructions.

5.   Storage of packed (unsold) equipment  

Storage package protection should be constructed such that 
mechanical damage to the equipment inside the package 
will not cause a leak of the refrigerant charge. The maximum 
number of pieces of equipment permitted to be stored 
together will be determined by local regulations.

Summary of Contents for KSV25CRG

Page 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Page 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Page 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Page 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Page 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Page 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Page 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Page 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Page 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Page 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Page 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Page 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Reviews: