Kelvinator KSV25CRG Installation Manual Download Page 18

18  Information servicing 

Kelvinator Air Conditioning

Information servicing

Checks to the area 

Prior to beginning work on systems containing flammable 
refrigerants, safety checks are necessary to ensure that the risk of 
ignition is minimised. For repair to the refrigerating system, the 
following precautions shall be complied with prior to conducting 
work on the system.

Work procedure 

Work shall be undertaken under a controlled procedure so as to 
minimise the risk of a flammable gas or vapour being present while 
the work is being performed.

General work area 

All maintenance staff and others working in the local area shall 
be instructed on the nature of work being carried out. Work in 
confined spaces shall be avoided. The area around the work space 
shall be sectioned off. Ensure that the conditions within the area 
have been made safe by control of flammable material.

Checking for presence of refrigerant

The area shall be checked with an appropriate refrigerant 
detector prior to and during work, to ensure the technician is 
aware of potentially flammable atmospheres. Ensure that the leak 
detection equipment being used is suitable for use with flammable 
refrigerants, i.e. no sparking, adequately sealed or intrinsically safe.

Presence of fire extinguisher

If any hot work is to be conducted on the refrigeration equipment 
or any associated parts, appropriate fire extinguishing equipment 
shall be available to hand. Have a dry powder or CO2 fire 
extinguisher adjacent to the charging area.

No ignition sources

No person carrying out work in relation to a refrigeration system 
which involves exposing any pipe work that contains or has 
contained flammable refrigerant shall use any sources of ignition 
in such a manner that it may lead to the risk of fire or explosion. 
All possible ignition sources, including cigarette smoking, should 
be kept sufficiently far away from the site of installation, repairing, 
removing and disposal, during which flammable refrigerant can 
possibly be released to the surrounding space. Prior to work taking 
place, the area around the equipment is to be surveyed to make 
sure that there are no flammable hazards or ignition risks. NO 
SMOKING signs shall be displayed.

Ventilated area

Ensure that the area is in the open or that it is adequately ventilated 
before breaking into the system or conducting any hot work.  
A degree of ventilation shall continue during the period that the 
work is carried out. The ventilation should safely disperse any 
released refrigerant and preferably expel it externally into the 
atmosphere.

Checks to the refrigeration equipment

Where electrical components are being changed, they shall be 
fit for the purpose and to the correct specification. At all times 
the manufacturer's maintenance and service guidelines shall 
be followed. If in doubt consult the manufacturer's technical 
department for assistance.

• 

 The following checks shall be applied to installations using 
flammable refrigerants: the charge size is in accordance with 
the room size within which the refrigerant containing parts are 
installed;

• 

 The ventilation machinery and outlets are operating 
adequately and are not obstructed;

• 

 If an indirect refrigerating circuit is being used, the secondary 
circuit shall be checked for the presence of refrigerant; marking 
to the equipment continues to be visible and legible.

• 

 Markings and signs that are illegible shall be corrected; 
refrigeration pipe or components are installed in a position 
where they are unlikely to be exposed to any substance which 
may corrode refrigerant containing components, unless the 
components are constructed of materials which are inherently 
resistant to being corroded or are suitably protected against 
being so corroded.

Checks to electrical devices

Repair and maintenance to electrical components shall include 
initial safety checks and component inspection procedures. If a 
fault exists that could compromise safety, then no electrical supply 
shall be connected to the circuit until it is satisfactorily dealt with. 
If the fault cannot be corrected immediately but it is necessary to 
continue operation, an adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so all parties 
are advised. 

Initial safety checks shall include: 

• 

 That capacitors are discharged: this shall be done in a safe 
manner to avoid possibility of sparking; 

• 

 That there no live electrical components and wiring are 
exposed while charging, recovering or purging the system; 

• 

That there is continuity of earth bonding.

Summary of Contents for KSV25CRG

Page 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Page 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Page 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Page 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Page 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Page 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Page 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Page 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Page 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Page 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Page 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Page 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Reviews: