5/2004 Manual for connection and operation of the EV-94 EB page 13 of 28
-
Press button 1 to validate the selection, the display shows “
Li
“ again.
-
When pressing button 1 again, the display will show “
FiLt
“ (Filter
= digital filter
).
-
Use button 2 and button 3 to select the desired filter [in sec.].
Selectable values: 0.01 ... 2.00 sec.
Explanation: this digital filter is a digital replica of a low pass filter.
Note: when using the input signal 0-50mV a filter value of at least 0.2 is recommended
-
Press button 1 to validate your value, the display shows “
FiLt
“ again.
Now your device is adjusted to your signal source. Now the only thing left to do is to adjust the outputs of the
device.
-
When pressing button 1 again, the display shows “
outP
“. (output)
For configuring the outputs of the EV-94 EB, please follow the instructions given in chapter 4.8.
4.3. Measuring temperature
(Pt100, Pt1000 RTD probes and thermocouple type J, K, N, S or T
)
This chapter describes how to configure the device for temperature measuring with the help of external plati-
num RTD probes or thermocouple probes. This instruction demands that you selected “
t.res
“ or “
t.tc
“ as your
desired input type like it is explained in chapter 4.1. The device has to display “
InP
“.
-
When pressing button 1 the display shows “
SEnS
“.
-
Use button 2 or button 3 (middle resp. right button) to select your desired input signal.
Display
Input signal
(RTD)
Notes
Pt0.1
Pt100
(3-wire)
Meas.-range: -50.0 ... +200.0 °C
(-58.0 ... + 392.0 °F)
Resolution: 0.1°
Pt1
Pt100
(3-wire)
Meas.-range: -200 ... + 850 °C
(-328 ... + 1562 °F)
Resolution: 1°
1000
Pt1000
(2-wire)
Meas.-range: -200 ... + 850 °C
(-328 ... + 1562 °F)
Resolution: 1°
Display
Input signal
(Thermocouples)
Notes
NiCr
NiCr-Ni (type K)
Meas.-range: -270 ... +1350 °C
(-454 ... + 2462 °F)
S
Pt10Rh-Pt (type S)
Meas.-range: -50 ... +1750 °C
(- 58 ... + 3182 °F)
n
NiCrSi-NiSi (type N)
Meas.-range: -270 ... +1300 °C
(-454 ... + 2372 °F)
J
Fe-CuNi (type J)
Meas.-range: -170 ... + 950 °C
(-274 ... + 1742 °F)
T
Cu-CuNi (type T)
Meas.-range: -270 ... + 400 °C
(-454 ... + 752 °F)
-
Validate the selected input signal by pressing button 1. The display shows “
SEnS
“ again.
-
When pressing button 1 again, the display will show “
Unit
“ (the unit you want to display).
-
Use button 2 and button 3 to select weather you want to display
°C
or
°F
.
-
Use button 1 to validate the selected unit, the display shows “
Unit
“ again.
-
Press button 1 to again, the display will be showing “
FiLt
“ (Filter
= digital filter
).
-
Use button 2 and button 3 for setting the desired filter-value [in sec.].
Selectable values: 0.01 ... 2.00 sec.
Explanation: this digital filter is a digital replica of a low pass filter.
-
Use button 1 to validate your selection, the display shows “
FiLt
“ again.
Now your device is adjusted to your signal source. Now the only thing left to do is to adjust the outputs of the
device.