background image

HEATING SYSTEM PREPARATION AND TIPS 

 

 

 

 

 

 

 

 

Page 3 

Always run heating system prior to power flushing to establish the problem areas such as cold spots on 
radiators or slow circulation, you can then make sure the strongest concentration of chemicals are 
directed to these problem areas. 

Before power flushing the system it is important to check the following: 

All radiator valves are fully open, both sides of radiator. Thermostatic rad valve heads should be 
removed and check the pins are not stuck down. Isolate electrical supply to circulating pump, 
regardless of whether or not this is the location for connecting the Flowclean pump to the heating 
system. 

Check that all zone valves are set to manual open and that if any anti-gravity check valves are fitted to 
the system, these are temporarily removed or by-passed to allow flow reversing action to be used, any 
bypass should also be closed. 

When flushing a vented system you will need to cap off both the cold feed and vent to avoid overflowing 
of the feed and expansion tank, in some cases you can create a temporary loop, connecting cold feed 
and vent together, which will then include these pipes in the flushing process. 

Please do note that capping off or looping pipes, by-passing check valves etc are temporary 
measures and will need to be reinstated after the power flushing procedure is finished. 

The dump hose should run into a foul sewer; a toilet, gully or drain are commonly used.                        
Care should be taken as contaminated water may well stain different surfaces. 

During the dumping process, if the mains water going in via the cold water inlet tap cannot keep up with 
what is being dumped out, stop dumping and allow water to return to required level: Do not adjust or 
restrict dump valve to try and compensate.                

Handy tips 

Your Flowclean pump is compatible with all approved chemicals, however it is important to make sure 
the correct chemicals are being used on the system you are working on, take care and read through 
chemical instructions carefully, aluminium heat exchangers, galvanised or stainless steel pipes will 
dictate which chemicals are suitable. 

If an acid based descaler is used then the system, including the Flowclean pump must be neutralised 
with the suggested neutralising agent prior to the final flush through with cold water.  
 
At all times during the flushing procedure the tank filling cap must be left off in order to allow the 
exhaust of acidic vapour created by the cleaning process. 
 
Maintain vigilance on the amount of foam produced. Do not overfill the tank by exceeding the maximum 
level marked clearly on the side of the tank. It is good practise to use waterproof dust sheets and 
replace end caps on hoses after use to prevent any unwanted spillages. 

 

In order to maintain continued flushing pump efficiency and reliability, it is of paramount importance that 
all equipment is thoroughly washed with clean water after every use. 
 
The flow diverter valve is situated on the top of the tank directly over the chemical fill point, the lever 
when in the correct position points in the flow direction set. (See page 5

 

for further detail) 

 

Summary of Contents for Anton Flowclean Plus

Page 1: ...USER MANUAL PLEASE READ THROUGH ALL INSTRUCTIONS BEFORE USE ...

Page 2: ... Unpacking Page 3 Heating system preparation and tips Page 4 Connections and controls Page 6 Connecting to heating system Page 7 Power flushing procedure Page 9 Technical data and safety Page 10 Spares and accessories ...

Page 3: ...fully remove your Flowclean Plus from the packaging and check the contents as follows Flowclean Plus pump with transport trolley Carry case for hoses and fittings Magnetic inline filter Supameg Compact System connection fitting kit and chemical funnel Quick guide instructions 2 x 3 metre flow and return hoses 2 x 3 metre dump and overflow hoses Page 2 Any shortages should be reported in writing di...

Page 4: ...taken as contaminated water may well stain different surfaces During the dumping process if the mains water going in via the cold water inlet tap cannot keep up with what is being dumped out stop dumping and allow water to return to required level Do not adjust or restrict dump valve to try and compensate Handy tips Your Flowclean pump is compatible with all approved chemicals however it is import...

Page 5: ...connection Right hand valve Return Left hand valve Flow Cold water inlet tap Please note correct position of drain tap on magnetic filter fitted using swivel coupling supplied to the return hose connection right hand side 3 position valves Dump Upward Closed Horizontal Recirculate Downward Return hose connection ...

Page 6: ...CONNECTIONS AND CONTROLS Page 5 The flow diverter valve points in the direction of flow Chemical fill point funnel provided Min Max Min Max level indicators Power On Off switch ...

Page 7: ...ms Feed and expansion tank Mains cold feed Connect at pump valve connections this method is most commonly used Connect at boiler connections this method is normally used when a new boiler is being fitted Connect at radiator valve connections this method is most commonly used where a combination or system boiler is present and pump access is difficult Bypass ...

Page 8: ... dumping out maintain water level in other words Continue dumping until dump water runs clear Step 6 Back to recirculation adding chemical Now set right hand valve return back to recirculate and turn off water inlet valve continue to recirculate with all radiator valves open Now add flushing chemicals to system using your chemical funnel on the front of your tank Step 7 Heating water To assist wit...

Page 9: ...umping until dump water runs clear or for approximately 10 15 minutes You will now need to test the pH levels to check dump water is now neutral this should read the same as a sample from the mains water supply to the building pH paper or electronic pH meters can be used Step 13 Adding inhibitor system protector You can now add your inhibitor protector to the system either using your chemical funn...

Page 10: ... in no way will any claims for any damages be entered into in any way whatsoever however caused SAFETY TIPS As with all large or heavy goods care should be taken to prevent injury Always follow safety guidelines laid out in the chemical manufactures instructions It is recommended that a RCD residual circuit device is used Regular inspection of power lead and plug is strongly recommended Dimensions...

Page 11: ...exchanger adaptor AFPHA Circulating pump head adaptor AIRG Laser infra red digital thermometer with belt pouch ASMC Supameg compact filter with valves for heating system use ASMC F Supameg compact filter with connection coupling for power flusher use AA15 HDH Liquid probe can be used with AIRG thermometer above Bahco 2971G Pump valve Pliers ...

Page 12: ...ng the details below UK Office Keison Products P O Box 2124 Chelmsford Essex CM1 3UP England Tel 44 0 330 088 0560 Fax 44 0 1245 808399 Email sales keison co uk Please note Product designs and specifications are subject to change without notice The user is responsible for determining the suitability of this product ...

Reviews: