background image

TECHNICAL DATA AND SAFETY 

 

 

 

 

 

 

 

 

Page 9 

In order to maintain continued flushing pump efficiency and reliability it is of 
paramount importance that all equipment is thoroughly washed with clean water 
after every use. 
 
12 Months parts and labour warranty subject to fair wear and tear and no misuse. 
 
The manufacturer and distributor reserve the right, that in the event of a fault claim 
they will repair or replace accordingly at their discretion. 
 
NOTE: - These notes are for guidance only and in no way will any claims for any 
damages be entered into in any way whatsoever, however caused. 
 
 

SAFETY TIPS 
 

As with all large or heavy goods, care should be taken to prevent injury. 
Always follow safety guidelines laid out in the chemical manufactures instructions.  
It is recommended that a RCD (residual circuit device) is used.                               
Regular inspection of power lead and plug is strongly recommended. 

 

Dimensions: W43 x D48 x H56 (cm)                                       
Weight: 18 KG with transport trolley                             
Tank capacity: 37 litres                                       
Compatible with all approved chemicals                 
Working fluid temperature up to 70ºC                     
Efficient cleaning up to 20 radiators                                                    
Flow rate: 5,400 ltrs/hr max 

                                                                 

0.45 HP motor with IP54 protection                              
Max working head: 2bar 

 

 

Summary of Contents for Anton Flowclean Plus

Page 1: ...USER MANUAL PLEASE READ THROUGH ALL INSTRUCTIONS BEFORE USE ...

Page 2: ... Unpacking Page 3 Heating system preparation and tips Page 4 Connections and controls Page 6 Connecting to heating system Page 7 Power flushing procedure Page 9 Technical data and safety Page 10 Spares and accessories ...

Page 3: ...fully remove your Flowclean Plus from the packaging and check the contents as follows Flowclean Plus pump with transport trolley Carry case for hoses and fittings Magnetic inline filter Supameg Compact System connection fitting kit and chemical funnel Quick guide instructions 2 x 3 metre flow and return hoses 2 x 3 metre dump and overflow hoses Page 2 Any shortages should be reported in writing di...

Page 4: ...taken as contaminated water may well stain different surfaces During the dumping process if the mains water going in via the cold water inlet tap cannot keep up with what is being dumped out stop dumping and allow water to return to required level Do not adjust or restrict dump valve to try and compensate Handy tips Your Flowclean pump is compatible with all approved chemicals however it is import...

Page 5: ...connection Right hand valve Return Left hand valve Flow Cold water inlet tap Please note correct position of drain tap on magnetic filter fitted using swivel coupling supplied to the return hose connection right hand side 3 position valves Dump Upward Closed Horizontal Recirculate Downward Return hose connection ...

Page 6: ...CONNECTIONS AND CONTROLS Page 5 The flow diverter valve points in the direction of flow Chemical fill point funnel provided Min Max Min Max level indicators Power On Off switch ...

Page 7: ...ms Feed and expansion tank Mains cold feed Connect at pump valve connections this method is most commonly used Connect at boiler connections this method is normally used when a new boiler is being fitted Connect at radiator valve connections this method is most commonly used where a combination or system boiler is present and pump access is difficult Bypass ...

Page 8: ... dumping out maintain water level in other words Continue dumping until dump water runs clear Step 6 Back to recirculation adding chemical Now set right hand valve return back to recirculate and turn off water inlet valve continue to recirculate with all radiator valves open Now add flushing chemicals to system using your chemical funnel on the front of your tank Step 7 Heating water To assist wit...

Page 9: ...umping until dump water runs clear or for approximately 10 15 minutes You will now need to test the pH levels to check dump water is now neutral this should read the same as a sample from the mains water supply to the building pH paper or electronic pH meters can be used Step 13 Adding inhibitor system protector You can now add your inhibitor protector to the system either using your chemical funn...

Page 10: ... in no way will any claims for any damages be entered into in any way whatsoever however caused SAFETY TIPS As with all large or heavy goods care should be taken to prevent injury Always follow safety guidelines laid out in the chemical manufactures instructions It is recommended that a RCD residual circuit device is used Regular inspection of power lead and plug is strongly recommended Dimensions...

Page 11: ...exchanger adaptor AFPHA Circulating pump head adaptor AIRG Laser infra red digital thermometer with belt pouch ASMC Supameg compact filter with valves for heating system use ASMC F Supameg compact filter with connection coupling for power flusher use AA15 HDH Liquid probe can be used with AIRG thermometer above Bahco 2971G Pump valve Pliers ...

Page 12: ...ng the details below UK Office Keison Products P O Box 2124 Chelmsford Essex CM1 3UP England Tel 44 0 330 088 0560 Fax 44 0 1245 808399 Email sales keison co uk Please note Product designs and specifications are subject to change without notice The user is responsible for determining the suitability of this product ...

Reviews: