5 Use and Operation
All rights reserved ©Kehua Hengsheng Co., Ltd.
93
Step 4
Disconnect OUTPUT switch, after the touch screen, LED indicators are all off, the maintenance can
be done.
During maintenance, it is strictly forbidden to close the OUTPUT switch.
----End
5.3.6 Switch to Inverter Power Supply from Maintenance Bypass
Before perform the operation of switching to inverter power supply from maintenance bypass, please
ensure that the system bypass input is normal.
Step 1
Close the BYPASS switch
→
POWER switch
→
external battery breaker
→
OUTPUT switch
successively.
Step 2
After the power supply normal and the energy flow on touch screen shows bypass output, place the
MAINTENANCE switch to OFF. At this time, the bypass supply power for load.
Step 3
Start the inverter system.
When the green indicator of all power module slow flicker, click
icon in main page to enter
ON/OFF page, click
ON
and then click
OK
icon to start the inverter. The UPS turns to inverter
output.
The inverter also can be started by ON combination button on the panel, generally, it is not suggested
to operate like this.
----End