background image

9

INSTALLATION GUIDE

Ideal installation locations include:
Indoor Unit

S

A location where there are no obstacles near inlet and outlet area.

S

A location which can bear the weight of indoor unit.

S

Do not install indoor units near a direct source of heat such as

direct sunlight or a heating appliance.

S

A location which provides appropriate clearances as outlined in

Fig. 4. Be sure to leave enough distance to allow access for

routine maintenance. The installation site should be 72” or more

above the floor.

S

Select a place away from potential electronic interference.

S

Select a place where the filter can be easily removed.

Outdoor Unit

S

A location which is convenient to installation and not exposed to

strong wind.

S

A location which can bear the weight of outdoor unit and where

the outdoor unit can be mounted in a level position.

S

A location which provides appropriate clearances as outlined in

Fig. 4.

S

Do not install the indoor or outdoor units in a location with

special environmental conditions.

S

Make sure the outdoor unit is installed in accordance with the

installation instructions and is convenient for maintenance and

repair.

S

See the refrigerant piping table for the maximum height

difference between indoor and outdoor units and the maximum

length of the connecting tubing.

INDOOR UNIT INSTALLATION

INSTALL MOUNTING PLATE

1. Carefully remove the mounting plate from the unit box.
2. The mounting plate should be located horizontally and level

on the wall. All minimum spacings shown in Fig. 2.

3. If the wall is block, brick, concrete or similar material, drill

.2” (5 mm) diameter holes and insert anchors for the

appropriate mounting screws.

4. Attach the mounting plate to the wall.

DRILL HOLE IN WALL FOR INTERCONNECTING

PIPING, DRAIN AND WIRING

Refrigerant Line Routing

The refrigerant lines may be routed in any of the four directions

shown in Fig. 6.
For maximum serviceability, it is recommended to have refrigerant

line flare connections and the drain connection on the outside of
the wall that the fan coil is mounted on.

    rear left.

left

rear left

right

rear right

A12585

Fig. 6

-

Refrigerant Line Routing

cut off
the hole

left

right

Fig. 7

-

Refrigerant Line Routing

If piping is going through the back:

1. Determine pipe hole position using the mounting plate as a

template. Drill pipe hole diameter per chart below. The

outside pipe hole is 1/2- in. (13 mm) min. lower than inside
pipe hole, so it slants slightly downward.

If piping is going to exit from the left rear, it is
recommended to field- fabricate piping extensions to get the

flare connections to the outside of the wall.

1/2 in. (13 mm) 

Min.

INDOOR

OUTDOOR

A07371

Fig. 8

-

Drill Holes

Table 15—Hole Diameter

Model Size

Hole Diameter

in. (mm)

9K, 12K, 18K, 24K

2.2 (56)

30K & 36K

2.75 (70)

If piping is going through the right or left side:

1. Use a small saw blade to carefully remove the

corresponding plastic covering on side panel and drill the
appropriate size hole where the pipe is going through the
wall. See Fig. 14.

2. Remove knockout (see Fig. 7).

NOTE

:

If required, a condensate pump is available for the

application.

OUTDOOR UNIT INSTALLATION

1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Excessive torque can break flare nut depending on

installation conditions.

Piping Connections to Outdoor Unit
IMPORTANT

:

Use refrigeration grade tubing ONLY. No other

type of tubing may be used. Use of other types of tubing will

void manufacturer’s warranty.

Make sure there is enough piping to cover the required length

between the outdoor and indoor unit.

Only use piping suitable for high side pressure for both high

side and low side connections.

Summary of Contents for DLFCAB

Page 1: ...ON GUIDE 9 INDOOR UNIT INSTALLATION 9 Install Mounting Plate 9 Drill Hole in Wall for Interconnecting Piping Drain and Wiring 9 OUTDOOR UNIT INSTALLATION 9 Piping Connections to Outdoor Unit 9 INSTALL...

Page 2: ...injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property...

Page 3: ...n 3 8 1 2 3 8 1 2 1 2 5 8 5 8 5 8 Liquid Pipe size connection type in 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 Table 3 Refrigerant Information DLFCAB DLCCAR DLFCHB DLCCHR System Size 9K 12K 9K 12K 18K 24K 30K...

Page 4: ...ype in 3 8 3 8 3 8 3 8 1 2 5 8 5 8 5 8 Liquid Pipe size connection type in 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 Table 5 Refrigerant Information DLFDAB DLCDAR DLFDHB DLCDHR System Size 9K 12K 9K 12K 18K 24K...

Page 5: ...ation must be used as the communication wire from the outdoor unit to the indoor unit Please use a separate shielded 16GA stranded control wire CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this c...

Page 6: ...A C B D D E E F H Fig 2 Indoor Mounting Plate Table 10 DLFCAB DLCCAR DLFCHB DLCCHR System Size 9K 12K 9K 12K 18K 24K 30K 36K Voltage 115 1 60 115 1 60 208 230 1 60 208 230 1 60 208 230 1 60 208 230 1...

Page 7: ...ing Only lbs 62 8 73 9 72 8 80 5 113 6 147 7 152 1 154 4 NET Weight Heat Pump lbs 71 7 77 2 78 3 86 114 7 142 2 154 4 161 Table 13 DLFDAB DLCDAR DLFDHB DLCDHR System Size 9K 12K 9K 12K 18K 24K 30K 36K...

Page 8: ...in 6 5 0 13m min 1 8m CEILING FLOOR Fig 4 Indoor Unit Clearances CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Outdoor Unit Clearances Table 14 Outdoor Clearances UNIT Minimum Value in mm A...

Page 9: ...The refrigerant lines may be routed in any of the four directions shown in Fig 6 For maximum serviceability it is recommended to have refrigerant line flare connections and the drain connection on th...

Page 10: ...ount outdoor power disconnect 2 Run power wiring from main box to disconnect per NEC and local codes Set outdoor unit in place 3 Remove field wiring cover from unit by removing screws 4 Connect condui...

Page 11: ...n piping and wiring to the wall as required Completely seal the hole in the wall cut off the hole left right Fig 14 Remove Knockouts Mounting plate Fixing hook Mounting plate A12408 Fig 15 Hang Indoor...

Page 12: ...n any liquid water Refer to Fig 19 and proceed as follows 1 Pump system down to 28 in of mercury and allow pump to continue operating for an additional 15 minutes 2 Close service valves and shut off v...

Page 13: ...ts work properly 3 Does the air deflection louver function properly 4 Does the drain work OUTDOOR UNIT 1 Are there unusual noises or vibrations during operation Explain Following Items To Customer Wit...

Page 14: ...it Terminal Block Indoor Unit Terminal Block Power to Indoor Unit Control to Indoor Unit Power to Indoor Unit Power from Outdoor Unit Control from Outdoor Unit CAUTION Attention Use Copper Conductors...

Page 15: ...open or short circuit F2 2 Outdoor ambient sensor open or short circuit F3 3 6 Outdoor tube sensor open or short circuit F4 4 5 Exhaust sensor open or short circuit F5 5 7 Overload limit drop frequen...

Page 16: ...national Comfort Products Lewisburg TN 37091 USA Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Edition Date 06 15 Catalog No 4...

Reviews: