CB4 PVC
CB1 PVC
CB3 PVC
Fig. 1
Free End Example
CB7 PVC
Kee
®
Guard
Termination
The beginning and end of every continuous run must have
one of three possible configurations:
Option 1:
(shown in Fig. 1 - Option 1) A CB7 PVC assembly
spaced 8’ from the following CB1
Option 2:
(Shown in Fig. 1 - Option 2) A KGU with a CB4 PVC
assembly and a KGU with a CB3 PVC as¬sembly 3’ 3’’ from the
CB4 PVC assembly or A KGU with a CB7 PVC assembly unless
fastened to a structural member.
Option 3:
(Shown in Fig. 2 - Option 3) Fasten the KeeGuard
rail into brickwork or steel using two Kee Klamp Type 61-8
(Wall Flange) OR two Kee Klamp type v (flange). The closest
upright should be placed no further than 8’ from the
wall or steel.
*Be sure to verify with your company representative
which ending option your system was provided with.
If you purchased shop drawings please follow the
layout on the drawings exactly.
Corners
At corners greater than or less than 90° where a run is
continuous, use Kee Klamp Type BC53-88 (Swivel Elbow).
Be sure the spacing is no greater than 8’ between the
uprights, with one upright being no further than 20’’ from
the corner. See Fig. 1.
S A F E T Y A T T H E H I G H E S T L E V E L
USA 800.851.5181 CN 877.505.5003
CB1 PVC
Counterbalance Assembly
CB1 PVC assemblies consist of one counterbalance and one
42” long 1-1/4” pipe. CB3 PVC assemblies consist of three
counterbalances and one 42” long 1-1/4” pipe. CB4 PVC
assemblies consist of four counterbalances and one 66’’
long 1-1⁄4’’ pipe. CB7 PVC assemblies consist of seven
counterbalances and one 66” long pipe.
CB3 PVC
CB4 PVC
*IMPORTANT NOTE: Only one (1) Kee Klamp TYPE 74-7 (Collar)
should be used each one (1) KeeGuard Type 440-7 (PVC Counter-
balance). The use of more than one Collar will result in not having
enough Collars to complete the job. Only one collar is necessary per
each PVC Counterbalance to create a safe and compliant system
saving you time and money.
CB7 PVC
Installation Instructions
1.
Be sure the locations for all uprights and counter-
balances are free from stone and debris. Kee Safety advises
that KeeGuard should not be installed during snowy or icy
weather unless all snow and ice is cleared first.
2.
Position a KGU (KeeGuard Upright). Angle of uprights are
adjustable between 90° and 79° from the horizontal. Connect
a CB4 PVC counterbalance assembly* (
see IMPORTANT NOTE
below
), to the KGU with the 66’’ long 1-1⁄4’’ pipe and tighten
the set screws to 29 lbs/ft (39 Nm). Install plug on end of
tube.
3.
Position a KGU at 4’ from the
first upright and con
nect a
CB3 PVC assembly with the 42’’ long 1-1⁄4’’ pipe and tighten
the set screws to 29 lbs/ft (39 Nm).
4.
Position a KGU at 8’ from the previous upright and connect
a CB1 PVC assembly with the 42’’ long 1-1⁄4’’ pipe and tighten
the set screws to 29 lbs/ft (39 Nm).
5.
Set the 1-1
⁄2’’ galvanized pipe into the Kee Klamp
Type
135-8 at the top and at the mid section of the uprights to
form two rails and tighten the set screws. Connect the
lengths of handrail together using Kee Klamp Type 14-8
(Straight Coupling) and tighten the set screws to 29 lbs/ft
(39 Nm). Be sure to stagger the joints of the horizontal rails.
Ideally the Type 14-8 (Straight Coupling) connections on the
mid rail and top rail should be offset by 8’.
6.
Continue along the roof edge repeating steps 4 & 5.
7.
At 90° corners, use Kee Klamp Type 15-8 (90
°
Elbow).
Ensure that an upright is located less than 20’’ from the
corner. The total length between uprights around the corner
must be no greater than 8’.
Fig. 2
Wall attachment example
KeeGuard Drawing
Just
contact us, at Kee Safety for custom configurations and
technical assistance toll free at (800) 851 5181.
Option 1
Option 2
Option 3
8’
6’4”
1’8”
11’4”
1’8”
8’
8’
42”
7’8”
42”
1’8”
3’3”
8’
8’