background image

CB4 PVC

CB1 PVC

CB3 PVC

Fig. 1

Free End Example

CB7 PVC

Kee

®

 Guard

Termination

The beginning and end of every continuous run must have 

one of three possible configurations:

Option 1:

 (shown in Fig. 1 - Option 1) A CB7 PVC assembly 

spaced 8’ from the following CB1  

Option 2:

 (Shown in Fig. 1 - Option 2) A KGU with a CB4 PVC 

assembly and a KGU with a CB3 PVC as¬sembly 3’ 3’’ from the 

CB4 PVC assembly or A KGU with a CB7 PVC assembly unless 

fastened to a structural member. 

Option 3:

 (Shown in Fig. 2 - Option 3) Fasten the KeeGuard 

rail into brickwork or steel using two Kee Klamp Type 61-8 

(Wall Flange) OR two Kee Klamp type v (flange). The closest 

upright should be placed no further than 8’ from the 

wall or steel.

*Be sure to verify with your company representative 

which ending option your system was provided with. 

If you purchased shop drawings please follow the 

layout on the drawings exactly.  

Corners

At corners greater than or less than 90° where a run is 
continuous, use Kee Klamp Type BC53-88 (Swivel Elbow). 
Be sure the spacing is no greater than 8’ between the 
uprights, with one upright being no further than 20’’ from 
the corner.  See Fig. 1.

S A F E T Y   A T   T H E   H I G H E S T   L E V E L

 

 

USA  800.851.5181    CN  877.505.5003   

CB1 PVC

Counterbalance Assembly 

CB1 PVC assemblies consist of one counterbalance and one 

42” long 1-1/4” pipe.  CB3 PVC assemblies consist of three 

counterbalances and one 42” long 1-1/4” pipe. CB4 PVC 

assemblies consist of four counterbalances and one  66’’ 

long 1-1⁄4’’ pipe. CB7 PVC assemblies consist of seven 

counterbalances and one 66” long pipe. 

CB3 PVC

CB4 PVC

*IMPORTANT NOTE: Only one (1) Kee Klamp TYPE 74-7 (Collar) 
should be used each one (1) KeeGuard Type 440-7 (PVC Counter-
balance). The use of more than one Collar will result in not having 
enough Collars to complete the job. Only one collar is necessary per 
each PVC Counterbalance to create a safe and compliant system 
saving you time and money.

CB7 PVC

Installation Instructions

1.  

Be sure the locations for all uprights and counter-

balances are free from stone and debris. Kee Safety advises 

that KeeGuard should not be installed during snowy or icy 

weather unless all snow and ice is cleared first. 

2.  

Position a KGU (KeeGuard Upright). Angle of uprights are 

adjustable between 90° and 79° from the horizontal. Connect 

a CB4 PVC counterbalance assembly* (

see IMPORTANT NOTE 

below

), to the KGU with the 66’’ long 1-1⁄4’’ pipe and tighten 

the set screws to 29 lbs/ft (39 Nm). Install plug on end of 

tube.

3.  

Position a KGU at 4’ from the

 first upright and con

nect a 

CB3 PVC assembly with the 42’’ long 1-1⁄4’’ pipe and tighten 

the set screws to 29 lbs/ft (39 Nm). 

4.

  

Position a KGU at 8’ from the previous upright and connect 

a CB1 PVC assembly with the 42’’ long 1-1⁄4’’ pipe and tighten 

the set screws to 29 lbs/ft (39 Nm). 

5. 

 Set the 1-1

⁄2’’ galvanized pipe into the Kee Klamp

 Type 

135-8 at the top and at the mid section of the uprights to 

form two rails and tighten the set screws. Connect the 

lengths of handrail together using Kee Klamp Type 14-8 

(Straight Coupling) and tighten the set screws to 29 lbs/ft 

(39 Nm). Be sure to stagger the joints of the horizontal rails.  

Ideally the Type 14-8 (Straight Coupling) connections on the 

mid rail and top rail should be offset by 8’.

6.  

Continue along the roof edge repeating steps 4 & 5. 

7.  

At 90° corners, use Kee Klamp Type 15-8 (90

°

 Elbow). 

Ensure that an upright is located less than 20’’ from the 

corner.  The total length between uprights around the corner 

must be no greater than 8’.

Fig. 2

Wall attachment example

KeeGuard Drawing

Just 

contact us, at Kee Safety for custom configurations and 

technical assistance toll free at (800) 851 5181.

Option 1

Option 2

Option 3

8’

6’4”

1’8”

11’4”

1’8”

8’

8’

42”

7’8”

42”

1’8”

3’3”

8’

8’

Reviews: