4.2
Sensor interface (SENSOR)
4.2.1
Connection example
Fig.4-3:
Connection example for sensor interface
1
... Data cable CAT5
4.2.2
Cable specification
To connect the sensor interface with the temperature module a shielded
non-“crossed” data cable of category 5 (CAT5, 1:1 connection) must be used.
Max. length: 60 m.
4.2.3
Plug specification
RJ45 connector: Modular 8-pole plug, shielded
The cable shielding must be connected plane with the shield cover of the plug.
An additional connection of the shield and the ground is not necessary.
4.3
EMC and wiring guidelines
Pay attention from the outset to careful wiring and shielding.
Further information: See system manual.
TM 240/A, TE 220/A for KeStudio U3
Connection and wiring
© KEBA 2011
Project engineering manual V1.10
15