Fig.5-3:
Removing the option module
5.3
Adding modules
The CP 263/x makes the following output available for up to 12 add-on mod-
ules:
Output power on the K-Bus (5 V):
10 W
Output power on the K-Bus (24 V):
45 W
To guarantee stable functioning of the module cluster the total power demand
("Power consumption 5 V on the K-Bus" and "Power consumption 24 V on the
K-Bus") on the added-on modules must not exceed the power values (Max.
output power K-Bus 5 V" and "Max. output power K-Bus 24 V") of the
CP 263/x specified in the technical data.
Information
For the calculation of the number of modules that can be added, the per-
formance values specified in the technical data of the respective project
engineering manual under "Power consumption 5 V on the K-Bus" and "Pow-
er consumption 24 V on the K-Bus" must be used.
Further information:
●
See system manual
Further information: See system manual.
Mounting and installation instructions
CP 263/S, CP 263/X
© KEBA 2014
Project engineering manual V1.01
22