25
Power unit
Info
All SubD connectors have screw sockets with UNC 4-40 thread (tight-
ening torque 0.4 Nm).
Shield connection rails 3 x 10 mm are available for strain relief / shield
connection of the control cables. Commercially available shield con-
nection clamps (screw- or spring type) of suitable size or cable ties can
be used on them.
4.1.1.3 Shield connection rail
Figure 8:
Shield connection rail (Mat.Nr. 00P6ZGG-0002)
For EMC conform installation of the power cables an shield connection rail is available as
option. Commercially available shield connection clamps for rails 3x10 mm can be used. Die
Shield connection clamps (screw or spring type) must match the to cable diameter and are
therefore not included.
4.2
Power unit
4.2.1 Description of the terminal blocks
4.2.1.1 Terminal block X1A
Terminals
Function
Permissible cable
cross section [mm²]
Strip length
[mm]
L1, L2, L3
Mains input 3-phase
0,75…16
18
H1, H2
Heater input 400 Vac (op-
tion)
0,25…6
15
RB+, RB-
external braking resistor
(option)
0,75…16
18
PE,
protection-/functional earth 4x M6; Depth of thread 10 mm;
Tightening torque 4.8 Nm
Figure 9:
Terminal strip X1A