3.3 Control terminal strip X2A
The control terminal strip is designed as a double, plug-in terminal strip with push in cage
connection. It contains 32 poles. The following instructions must be observed at connection:
ATTENTION
Prevent eMC malfunctions
• Use shielded / drilled cables
• Lay shield on one side of the inverter onto earth potential
• Lay control and power cable separately (about 10...20 cm apart);
Lay crossings in a right angle (in case it cannot be prevented)
3.3.1 Assembly of the wires
Assembly of connecting wires with wire-end ferrules
according to DIN46228/4
Assembly of connecting wires without
wire-end ferrules
Cross-section /
AWG
Metal sleeve
length
Stripping
length
Cross-section / AWG
Stripping length
0.50 mm
2
/ 21
10 mm
12 mm
0.14 1.5mm2 , 25 16
10 mm
0.75 mm
2
/ 19
12 mm
14 mm
Connecting wires rigidy and flexible
1.00 mm
2
/ 18
12 mm
15 mm
Table 3:
Assembly of connecting wires without wire-end ferrules
•
Press pusher by hand. Insert connecting wires into the respective hole, that no single wires can be seen
from the outside or bend outward. A first resistance must be overcome when inserting. Release the pusher.
•
Check that the connecting wire is fixed and can not be pulled-out. It is important to ensure that the con
-
necting wire and not the insulation is clamped. The connecting wire can also be inserted without press-
ing the pusher in case of cross-sections upto 1.00 mm².
front view
Side view
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
b)
a)
a) Pusher
b) Connecting wire hole
Figure 7:
Assembly of the wires
ATTENTION
A safe clamping can not be guaranteed when using shorter wire-end
ferrules.
KEB generally recommends the use of wire-end ferrules in industrial environments.
19
CONTROL CIRCUIT ANALOG/DIGITAL