6
Certification
6.1 ce-Marking
CE marked drive converters and servo drives were developed and manufactured to
comply with the regulations of the Low-Voltage Directive 2006/95/EC and EMC directive
(2004/108/EC). The harmonized standards of the series
were used.
6.2 functional safety
Drive converters / servos with functional safety are marked with the FS logo on the
nameplate. These units are designed and manufactured in accordance with the Ma-
chine Directive (2006/42/EC). The harmonized standard of the series
is
used.
6.2.1 UL Marking
Acceptance according to UL is marked at KEB
drive converter
s
with the adjacent logo on the nameplate.
To be conform according to UL for use on the North American and Canadian Market the
following additionally instructions must be observed (original text of the UL-File):
• “Only for use in WYE 480V/277V supply sources”
• Operator and Control Board Rating of relays (30Vdc.:1A)
• "Maximum Surrounding Air Temperature 45
°
C"
• “Internal Overload Protection Operates prior to reaching the 200% of the Motor Full
Load Current”.
• For 480V rated models:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Sym-
metrical Amperes, 480 Volts Maximum, see instruction manual for Branch Circuit
Protection details"
and
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms
Symmetrical Amperes, 480 Volts Maximum when protected by CC, J or RK5 Class
Fuses", see instruction manual for maximum fuse sizes".
• For 240V rated models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Sym-
metrical Amperes, 240 Volts Maximum, see instruction manual for Branch Circuit
Protection details“
and
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms
Symmetrical Amperes, 240 Volts Maximum when protected by CC, J or RK5 Class
Fuses“, see instruction manual for maximum fuse sizes“.
continued on the next page
46