![KEB COMBIVERT G6 series Programming Manual Download Page 15](http://html2.mh-extra.com/html/keb/combivert-g6-series/combivert-g6-series_programming-manual_3858074015.webp)
15
Process Data Mapping
Id-Text
Name
Parameter index
fb13
PD out type
0x218D
Type
ARRAY
Subindex 0
Meaning
Number of subindices of this object
Data length
8 bit
Access
read
Coding
8
Standard value:8
Note
-
Subindex 1...8
Meaning
The value specifies the parameter type of the selected PD parameter.
Data length
8 bit
Access
read / write
Coding
0: off (no parameter type defined)
1: Long (32bit)
2: Word (16bit)
3: Byte (8 bit)
Standard value:0
Note
-
Id-Text
Name
Parameter index
fb14
PDO out count
0x218E
Meaning
Sets the number of PD-out objects
Type
Variable
Data length
8 bit
Access
read / write
Coding
0...8
Standard value:0
Note
Is automatically set to 0 when changing the parameters fb10...fb13.
Summary of Contents for COMBIVERT G6 series