GB - 7
Preface
1.6
Part code
27.F5. A B U-9 0 0 A
Cooling
0, 5, A, F Heat sink (standard)
1, B, G
Flat rear
2, C, H
Water-cooling system
3, D, I
Convection
Encoder interface
0:none
Switching frequency; short time current limit; overcurrent limit
0 2 kHz; 125 %; 150 % 5 4 kHz; 150 %; 180 % A 8 kHz; 180 %; 216 % F
16 kHz; 200 %; 240 %
1 4 kHz; 125 %; 150 % 6 8 kHz; 150 %; 180 % B 16 kHz; 180 %; 216 % G
2 kHz; 400 %; 480 %
2 8 kHz; 125 %; 150 % 7 16 kHz; 150 %; 180 % C 2 kHz; 200 %; 240 % H
4 kHz; 400 %; 480 %
3 16 kHz; 125 %; 150 % 8 2 kHz; 180 %; 216 % D 4 kHz; 200 %; 240 % I
8 kHz; 400 %; 480 %
4 2 kHz; 150 %; 180 % 9 4 kHz; 180 %; 216 % E 8 kHz; 200 %; 240 % K
16 kHz; 400 %; 480 %
Input identification
0 1ph 230 V AC/DC 5 400 V class DC A 6ph 400 V AC
1 3ph 230 V AC/DC 6 1ph 230 V AC B 3ph 600 V AC
2 1/3ph 230 V AC/DC 7 3ph 230 V AC C 6ph 600 V AC
3 3ph 400 V AC/DC 8 1/3ph 230 V AC D 600 V DC
4 230 V class DC
9 3ph 400 V AC
Housing type A, B, D, E, G, H, R, U, W, P
Internal options (A...D with STO relay according to EN954-1 / 1997)
0, A
none
B
Braking transistor without resistance monitoring
1, 5
Braking transistor with resistor monitoring
2, C
integrated EMC filter
3, D
Braking transistor without resistance monitoring and EMC filter
7
Braking transistor with resistor monitoring and EMC filter
Control type
A APPLICATION
K like A with safety technology
C COMPACT (controlled frequency inverter)
E SCL
P like E with safety technology
G GENERAL (controlled frequency inverter)
H ASCL
L like H with safety technology
MMULTI (regulated, field-oriented frequency inverter for three-phase asynchronous mo-
tors)
S SERVO (regulated frequency inverter for synchronous motors)
Series F5/F6
Inverter size
Summary of Contents for COMBIVERT F6
Page 2: ......