KE2 Compressor
Sequencer OEM
pn 21768
Quick Start Guide
Remote Display -
Variables Menu - Single Group
When not in a menu, press
or
to go through the Variables abbreviations.
Press
to view a Variable in real time.
Press
to return to the previous screen.
Abbrev. Full Name
Description
Prs
SuCTIOn PReSSuRe
Suction Pressure as read by the controller.
SUt
SuCTIOn TemPeRaTuRe
Suction Temperature as read by the controller.
SAt
SaTuRaTIOn TemPeRaTuRe
Saturated Suction Temperature as calculated by the controller.
SHt
SUPERHEAT
Suction Superheat as calculated by the controller.
dPr
DISCHaRGe PReSSuRe
Discharge Pressure as read by the controller.
dSt
DISCHaRGe TemPeRaTuRe
Discharge Temperature as read by the controller.
dSA
DISCHaRGe SaTuRaTIOn TemPeRaTuRe
Discharge Saturation Temperature as calculated by the controller.
dSH
DISCHaRGe SuPeRHeaT
Discharge Superheat as calculated by the controller.
iP1
IP OCTeT 1
First three digits of the IP address.
iP2
IP OCTeT 2
Second three digits of the IP address.
iP3
IP OCTeT 3
Third three digits of the IP address.
iP4
IP OCTeT 4
Fourth three digits of the IP address.
FiR
FIRmwaRe VeRSIOn
Current firmware version on the controller.
Remote Display -
Setpoints Menu - Single Group
When not in a menu, press and hold
until SA is shown.
Press
or
to go through the setpoint abbreviations.
Press
to view the current setpoint value. Press
or
to change the setpoint.
Press and hold
to save.
For numerical setpoints, pressing
once will change the digit that is being modified.
Press
to return to the previous screen. When viewing a setpoint value, press
to return to the previous screen without saving.
Abbrev. Full Name
Min
Max
Default
Description
SA
KE2 SMART ACCESS
diS
EnA
diS
Turn KE2 Smart Access on or off: EnA to enable / diS to
disable KE2 Smart Access.
dHC
DHCP mODe
diS
EnA
diS
Turn DHCP mode on or off: EnA to enable / diS to disable
DHCP mode.
SyS
SySTem On/OFF
oFF
on
oFF
Allow rack to run or put into system off: on to run / oFF to
pump down rack and put into system off.
PSP
TaRGeT SuCTIOn
PRESSURE
0.0 psig
150.0 psig
①
25.0 psig
②
Suction pressure the controller will work to maintain.
CLA
CLEAR ALARMS
Press and hold ENTER to clear all active alarms.
PAS
weB PaSSwORD ReSeT
Press and hold ENTER to reset browser password.
①
R-410A = 300.0 psig, R-744 = 500.0 psig.
②
R-744 =250.0 psig
Remote Display - Menus and Parameters
When not in alarm or off, displays Group 1 Suction Pressure.
Abbreviation Full Name
Description
oFF
System Off
All groups are in System Off mode.
oF1
System Off – Group 1
Group 1 is in System Off mode.
oF2
System Off – Group 2
Group 2 is in System Off mode.